Specification

LDN6 SWW
DOWNLIGHTING: One Lithonia Way Conyers, GA 30012 Phone: 800-705-SERV (7378) www.lithonia.com © 2020-2022 Acuity Brands Lighting, Inc. All rights reserved. Rev. 05/12/22
LDN6 SWW
EMERGENCY BATTERY PACK OPTIONS - FIELD INSTALLABLE
Battery Model Number Wattage Runtime (Minutes) Lumen Output* @ 120 Lumens/Watt Other
ILB CP07 2H A 7W 120 840 Storm Shelter / 2 Hour Runtime
ILB CP10 A 10W 90 1200
ILBLP CP10 HE SD A
+
10W 90 1200 Title 20, Self Diagnostic
ILBLP CP15 HE SD A
+
15W 90 1800 Title 20, Self Diagnostic
ILB CP20 HE A 20W 90 2400 Title 20
ILB CP20 HE SD A 20W 90 2400 Title 20, Self Diagnostic
ILBHI CP10 HE SD A
+
10W 90 1200 347-480V AC Input, Title 20, Self Diagnostic
ILBHI CP15 HE SD A
+
15W 90 1800 347-480V AC Input, Title 20, Self Diagnostic
All the above are UL Listed products that are certified for field install external/remote to the fixture.
* Minimum delivered lumen output to assist in product selection for increased fixture mounting height.
+
The CP10 delivered emergency illumination outperforms legacy 1400 lumen fluorescent emergency ballast.
Please contact us at productsupportemergency@acuitybrands.com for any Emergency Battery related questions.
Accessories: Order as a separate catalog number.
LO6AR ** TRIM 6" clear, specular reflector (** specify finish LS, LSS, or LS)
LO6WR TRIM 6" white reflector
LO6BR TRIM 6" black reflector
LW6AR ** TRIM 6" wallwash clear, specular reflector (** specify finish LS, LSS, or LS)
LW6WR TRIM 6" wallwash white reflector
LW6BR TRIM 6" wallwash black reflector
GRA68 JZ Oversized trim ring with 8" outside diameter
SCA6 Sloped Ceiling Adapter. Degree of slope must be specified (5D, 10D, 15D, 20D, 25D, 30D). Ex: SCA6 10D.
UL924 Sequence of Operation
The below information applies to all nLight AIR devices with an EM option.
EM devices will remain at their high-end trim and ignore wireless lighting control com-
mands, unless a normal-power-sensed (NPS) broadcast is received at least every 8 seconds.
Using the CLAIRITY+ mobile app, EM devices must be associated with a group that includes
a normal power sensing device to receive NPS broadcasts.
Only non-emergency rPP20, rLSXR, rSBOR, rSDGR, and nLight AIR luminaires with version
3.4 or later firmware can provide normal power sensing for EM devices. See specification
sheets for control devices and luminaires for more information on options that support
normal power sensing.
HOW TO ESTIMATE DELIVERED LUMENS IN EMERGENCY MODE
Use the formula below to estimate the delivered lumens
in emergency mode
Delivered Lumens = 1.25 x P x LPW
P = Ouput power of emergency driver. P = 10W for PS1055CP
LPW = Lumen per watt rating of the luminaire. This information is available
on the ABL luminaire spec sheet.
The LPW rating is also available at Designlight Consortium.
LUMEN OUTPUT MULTIPLIERS - FINISH
Specular (LS) 1.05
Semi-specular (LSS) 1.00
Matte diffuse (LD) 0.85
LUMEN OUTPUT MULTIPLIERS - CCT
3000K 3500K 4000K 5000K
0.98 1.0 1.01 1.03
LUMEN OUTPUT MULTIPLIERS - CRI
80 1.0
90 0.874