Brochure

Table Of Contents
© 2017 Littelfuse, Inc.
Specifications are subject to change without notice.
Revised: 03/03/17
Radial Lead Fuses
TE5
®
Fuse > Time-Lag Fuse > 400 Series
400 Series, TE5
®
Fuse, Time-Lag
Agency Approvals
Agency Agency File Number Ampere Range
E67006 0.50A – 6.3A
PS
E
JET1896-31007-2001
JET1896-31007-1006
1A – 5A
6.3A
40026355 0.50A – 6.3A
CQC09012031624 0.50A – 6.3A
SU05024-9004 0.50A – 6.3A
SU05024-9003 1A – 2.5A
SU05024-9001 3.15A
SU05024-10003 4A – 5A
SU05024-9002 6.3A
Features
Electrical Characteristics
Halogen free, Lead-free
and RoHS compliant
Reduced PCB space
requirements
Direct solderable or plug-
in versions
Low internal resistance
Shock safe casing
Vibration resistant
High Breaking Capacity
up to 130A at 250VAC
Internationally approved
% of Ampere
Rating
Opening Time
150% 1 Hour, Minimum
210% 120 Secs., Maximum
275% 400 ms, Minimum; 10 Secs., Maximum
400% 150 ms, Minimum; 3 Secs., Maximum
1000% 20 ms, Minimum; 150 ms, Maximum
Electrical Characteristics
Amp
Code
Rated
Current
Rated
Voltage
(V)
Breaking
Capacity
Nominal
Cold
Resistance
(Ohms)
Voltage
Drop
1.0×I
N
max. (mV)
Power
Dissipation
1.0×I
N
max. (mW)
Melting
Integral
10×I
N
max. (A
2
s)
Agency Approvals
PS
E
0.5 0.5A 250
130A
@250VAC
0.1950 165 297 2.170
x x x x
0800 0.8A 250 0.1003 116 387 6.720 x x x x
110 0 1.00A 250 0.0808 89 432 10.70 x x x x x
112 5 1.25A 250 0.0562 76 411 14.44 x x x x x
116 0 1.60A 250 0.0384 76 601 21.75 x x x x x
1200 2.00A 250 0.0292 75 758 46.00 x x x x x
1250 2.50A 250 0.0216 61 683 61.94 x x x x x
1315 3.15A 250 0.0167 55 921 101.61 x x x x x
1400 4.00A 250 0.0124 65 936 133.40 x x x x x
1500 5.00A 250 0.0098 56 948 216.50 x x x x x
1630 6.30A 250 0.0072 48 926 323.08 x x x x x
* Per VDE, approved breaking capacity is at 100A, 250VAC
RoHS
The 400 Series TE5
®
Fuse is a Time-Lag type subminiature
fuse and designed for overcurrent protection. It is 250V
rated and designed in accordance to IEC 60127-3.
Description
Applications
Battery chargers
Consumer electronics
Power supplies
Industrial controllers
Pb
PS
E
Application testing is strongly recommended.
Additional Information
Datasheet
Samples
Resources