Product Overview

littelfuse.com © 2015 Littelfuse POWR-GARD
®
Products
Rev: 082715
POWR-GARD
®
Fuse Datasheet
1 of 3
Part Numbering System
SERIES AMP
PACKAGE
QUANTITY
CATALOG
NUMBER
ORDERING
NUMBER
0KLK 1/8 10 0KLK.125 0KLK.125T
0KLK 5 100 0KLK005 0KLK005.H
Specifications
Voltage Rating: 600 Vac / 500 Vdc
Amperage Rating:
1
/10,
1
/8,
2
/10,
1
/4,
3
/10,
1
/2,
3
/4, 1, 1
1
/2, 2, 2
1
/2, 3,
3
1
/2, 4, 5, 6, 7, 8, 9,10, 12, 15, 20, 25, 30
Interrupting Ratings: AC: 100 kA
200 kA Littelfuse self-certified
DC: 50 kA
Material: Body: Melamine / Caps: Copper Alloy
Operating Temperature: See Rerating Curve
Approvals: UL 248-14 Listed (File: E10480)
CSA Certified (
File: LR29862)
QPL (File: F60C)
CE
Country of Origin: Mexico
Environmental: RoHS Compliant
Description
Fast-Acting, High-Interrupting Capacity, Current-Limiting
Type Fuse. Especially suited for control circuits, street
lighting, HID lighting, computers, and other applications
without high in-rush currents.
Features/Benefits
UL approved
1/10 - 30 A ratings available
100,000 A Interrupting Rating
Applications
Control Circuits
Street lighting, HID lighting
Computers
Dimensions Inches (mm)
Recommended Fuse Holders
Littelfuse LFPSM Dead-Front Series
Littelfuse LEB Series
Littelfuse L60030M Series
Web Resources
Download CAD drawings and other technical information:
littelfuse.com/klk
KLK SERIES 10x38 FUSES
600 Vac/500 Vdc •
1
/
10
-30 A • Fast Acting
0KLK xxx H
Package Quantity
Series
Amp Code
T = 10
H = 100
Refer to Amp Code
Column in Electrical
Specifications Table
1
Cartridge and Axial Lead Fuses
©2015 Littelfuse, Inc.
Specifications are subject to change without notice.
Revised: February 20, 2015
KLK Series
AC > Fast-Acting Type > KLK Series
KLK Series, AC, Fast-Acting Midget/5AG Size Fuse
Agency Approvals
Agency Agency File Number Ampere Range
E10480 .3A - 30A
®
LR 29862 .3A - 30A
QPL
F60C
Electrical Characteristics for Series
QPL
Fast-Acting, High-Interrupting Capacity, Current-Limiting
Type Fuse. Especially suited for control circuits, street
lighting, H.I.D. lighting, computers, and other applications
without high in-rush currents.
% of Ampere
Rating
Ampere Rating Opening Time
100% 0–30 Until temp stabilizes
135% 0–30 1 hours, Maximum
200% 0–30 2 minutes, Maximum.
Ordering
Number
Amp
Rating
(A)
Max
Voltage
Rating
(V)
Interrupting
Rating
Nominal
Cold
Resistance
(Ohms)
Agency Approvals
QPL
KLK .100
.100
600 100,000
amperes
(capable of
200,000) at
600VAC.
85.5
x x x
KLK .125
.125 65.0
x x x
KLK .200
.200 30.9
x x x
KLK .250
.250 22.0
x x x
KLK .300
.300 16.2
x x x
KLK .500
.500 7.99
x x x
KLK .750
.750 .398
x x x
KLK 001
1 .249
x x x
KLK 01.5
1. 5 .132
x x x
KLK 002
2 .129
x x x
KLK 02.5
2.5 .0989
x x x
KLK 003
3 .0773
x x x
KLK 03.5
3.5 .0613
x x x
KLK 004
4 .0511
x x x
KLK 005
5 .0357
x x x
KLK 006
6 .0261
x x x
KLK 007
7 .0205
x x x
KLK 008
8 .0194
x x x
KLK 009
9 .0166
x x x
KLK 010
10 .0128
x x x
KLK 012
12 .0103
x x x
KLK 015
15 .0073
x x x
KLK 020
20 .00421
x x x
KLK 025
25 .00329
x x x
KLK 030
30 .00267
x x x
Electrical Specifications by Item
®
Temperature Rerating Curve
Product Characteristics
Military Type F60C
Interrupting Rating
200,000 amperes at 500VAC
150,000 amperes at 500vDC
38.1
(1.50")
10.31
(.406")
Dimensions
Description
-60°C -40°C -20°C 0°C 20°C 40°C 60°C 80°C 100°C 120°C 140°C
-76°F -40°F -4°F 32°F 68°F 104°F 140°F 176°F 212°F 248°F 284°F
AMBIENT TEMPERATURE
60
40
20
0
PERCENT OF UPRATING
0
20
40
60
PER
CENT OF DOW
NRATIN
G
Temperature Derating Curve (Temperature
of Air Immediately Surrounding Fuse)

Summary of content (3 pages)