Cut Sheet

21
Cartridge and Axial Lead Fuses
©2009 Littelfuse, Inc.
Specifications are subject to change without notice.
Revised: August 12, 2009
CCMR Series
Class CC* Fuses > CCMR, KLDR and KLKR Series
Class CC fuses CCMR, KLDR and KLKR Series
Agency Approvals
Agency Agency File Number Ampere Range
E81895
0.1 - 30A (KLDR/KLKR)
0.2 - 60A (CCMR)
®
LR 29862 0.1 - 30A
Notes:
KLKR Series: UL listed Fast-Acting Class CC per UL 248 and CSA Certified
KLDR Series: UL listed Time-Delay Class CC per UL 248 and CSA Certified.
CCMR Series: UL listed Time-Delay Class CC per UL 248 and CSA Certified,
and 35-60A UL Listed Time-Delay Class CD.
Electrical Characteristics for Series
Fast-Acting KLKR fuses provide fast-acting protection to
equipment containing surge sensitive components. Use
KLKR Fuses for non-inductive loads not requiring time-
delay.
CCMR fuses (formerly KLMR) are specifically designed
to withstand sustained starting currents of small motors.
The CCMR Fuses provide short-circuit protection for motor
branch-circuits.
KLDR fuses are specifically designed to withstand
the momentary high magnetizing currents of control
transformers, solenoids, and similar inductive loads.
% of Ampere
Rating
Ampere Rating Opening Time
110% 0-30A 15 minutes, Minimum
135% 0-30A 1 hour, Maximum
200% 0-30A 4 minutes, Maximum
200% Time-delay 12 seconds, Minimum
®
Product Characteristics
Voltage Rating
AC: 600 Volts
DC: 250 Volts (CCMR 0.2 – 2A)
(CCMR 4.5 – 10A)
(CCMR 35 – 60A)
300 Volts (CCMR 2.25 – 4A)
300 Volts (KLDR)
300 Volts (KLKR)
500 Volts (CCMR 2 - 30A)
RoHS compliant items
KLKR - 0.1A - 30A
CCMR - 25A and 30A
KLDR - 0.1A - 7.5A, 25A and 30A
38.1 mm
(1.50")
6.4 mm
(.25")
12.7 mm
(.50")
10.3 mm
(.41")
0-30A
3.2 mm
(.125")
21.6 mm
(.850")
47.8 mm
(1.880")
35-60A
Dimensions
Description

Summary of content (4 pages)