Submittal Sheet

© 2018 Littelfuse Protection Relays & Controls
www.littelfuse.com/
Rev: 0-A-000016
Time Delay Relays
Dedicated - HVAC
www.littelfuse.com/t2d120a15m
Rev: 1-A-081618
T2D120A15M
Lockout
Wiring Diagram
Description
The T2D Series provides protection against short cycling of
compressors and other motors. At the end of each operation, a
lockout delay prevents restarting the compressor or motor until
the delay is completed.
Operation (Lockout with Random Start)
Connection #1: Upon application of input voltage, a random
start time delay begins. At the end of this time delay, the output
is energized.
Lockout Delay: Input voltage must be applied prior to and
during timing. When the thermostat or initiate switch opens,
the output de-energizes and the lockout time delay begins. At
the end of the lockout delay, the output is energized allowing
the load to immediately energize when the initiate switch or
thermostat closes.
Connection #2: Upon application of input voltage and closure
of initiate switch, the time delay begins. At the end of the time
delay, the output is energized and remains energized until power
is removed.
Reset: Removing power resets the output and the time delay.
Features & Benefits
FEATURES BENEFITS
Lockout delay Prevents rapid cycling of compressor
Random start delay Prevents low voltage starting
Analog circuitry Repeat Accuracy + / - 1%
Compact design Allows flexiblility for OEM applications
1A steady, 10A
inrush output
Provides 100 million operations in typical conditions.
Totally solid state and
fully encapsulated
No moving parts to arc and wear out over time and
encapsulated to protect against shock, vibration
and humidity
L1 N/L2
L1 N/L2
V = Voltage
L = Load
S1 = Initiate Switch or Thermostat
RANDOM START PLUS LOCKOUT
DELAY-ON-MAKE
Accessories
P1023-6 Mounting bracket
The 90° orientation of mounting slots makes
installation/removal of modules quick and easy.
P1015-64 (AWG 14/16)
Female Quick Connect
These 0.25 in. (6.35 mm) female terminals are
constructed with an insulator barrel to provide
strain relief.
P1015-18 Quick Connect to Screw Adapter
Screw adapter terminal designed for use with
all modules with 0.25 in. (6.35 mm) male quick
connect terminals.
C103PM (AL) DIN Rail
35 mm aluminum DIN rail available in a 36 in.
(91.4 cm) length.
P1023-20 DIN Rail Adapter
Allows module to be mounted on a 35 mm DIN
type rail with two #10 screws.

Summary of content (2 pages)