Service Manual

25
3 Troubleshooting (continued)
Table 3A Troubleshooting Chart - No Display
FAULT CAUSE CORRECTIVE ACTION
No Display
- No 120 VAC supplied to unit.
Check external line switch, fuse, or breaker.
Check position of ON/OFF switch. Turn switch to the
ON position.
Check 120 VAC through the ON/OFF switch.
Check wiring harness connection between display
board and main control board. Connect harness at both
points.
- No voltage through the switch. Replace switch.
- Bad display board. Replace board.
- Bad main control board. Replace the main control board.
- Blown fuse. Replace fuse F3 on the main control board, see
page 24 of this manual.
No Burner
Operation
- Main control board temperature set point
satisfied.
Review temperature setting.
- Remote thermostat satisfied. Review remote thermostat setting.
- Unit locked out on fault.
• Consult display for specific fault. Refer to fault
descriptions on pages 28 - 35 of this manual for
corrective actions.
Unit Does Not
Modulate Above
50%
- Water heater controlled by BMS.
Check BMS parameter settings. Optional PC software
required.
- Flue sensor open.
Verify that the flue sensor is located in the flue outlet.
Check wiring connections at the flue sensor.
Check the resistance of the flue sensor and compare
to Table 3D on page 26 of this manual.
Service Manual