1 Maintenance schedule
5
User’s Information Manual
Service technician
(Refer to the Copper-Fin Installation and
Service manual)
General:
Address reported problems
Inspect interior; clean and vacuum if
necessary;
Check for leaks (water, gas, flue)
• Examine venting system
Check system water pressure/
system piping/expansion tank
Check control settings
Check wiring connections
Flame inspection (stable, uniform)
Check flue gas passageways
Inspect and clean the burner
Perform start-up check-out and
performance verification. Refer to
the Startup section in the Copper-
Fin Installation and Service manual
If combustion or performance
indicate need:
Clean heat exchanger
Remove and wash burner
Annual Startup
Owner maintenance
Daily
Check appliance area
• Check pressure/temperature
gauge
Monthly
Check vent piping
Check relief valve
Periodically
Test low water cutoff (if used)
Reset button (low water cutoff)
Every
6 months
Check appliance piping (gas and
water) for leaks
Operate relief valve
End
of season
months
Shut appliance down (unless
boiler used for domestic hot
water)