Install Instructions

31
4 Water connections (continued)
A buffer tank is an effective way to enhance a small system load
and increase heating system efficiency (see FIG. 4-8 on page 36
of this manual). Buffer tanks add water volume to the system
and act as a flywheel to absorb the additional Btu’s provided by
the boiler when only a single zone of a large system is calling
for heat.
To calculate the proper buffer tank size for a multiple zone
system:
(Run Cycle) (Output - Minimum System Load)
(Temp. Rise) (8.33) (60 Min.)
CFN2067
Min. Load = 100,000 Btu/Hr
Min. Boiler Output = 850,000 Btu/Hr
Cycle Time = 10 Min
Temp. Rise = 38
(10)(850,000 – 100,000) / (38)(8.33)(60) = 395 Gallons
Installation & Service Manual
Pump Maintenance: Inspect the pump every six (6) months
and oil as necessary. Use SAE 30 non-detergent oil or lubricant
specified by the pump manufacturer.
The boiler is recommended for installation in a primary/
secondary piping system. This type of system uses a separate
boiler circulating pump to supply flow to and from the boiler
only. The secondary pump is sized based on the head loss of the
boiler and related pipe and fittings in the secondary loop only.
A properly sized primary system pump provides adequate flow
to carry the heated boiler water to radiation, air over coils,
etc. The fittings that connect the boiler to the primary system
should be installed a maximum of 12 inches (0.30m) (or 4 pipe
diameters) apart to ensure connection at a point of zero pressure
drop in the primary system. There should be a minimum of
10 pipe diameters of straight pipe before and after the boiler
secondary loop connections to prevent turbulent flow at the
secondary loop connections. The secondary loop piping to and
from the boiler must have a fully ported ball valve installed in
both the supply and return side piping. The ball valves must
be fully ported having the same inside diameter as the installed
piping. The ball valve in the piping supplying water to the boiler
will only be used as a service valve. The ball valve installed in
the discharge from the boiler back to the primary system will be
used to adjust boiler flow and temperature rise to ensure proper
performance.
The boiler primary piping system must have a circulator
installed in the main system loop to carry the heated boiler
water to the point of use in the main system.
Multiple boilers may also be installed with a primary/secondary
manifold system. Multiple boilers should be connected to the
common manifold in reverse return to assist in balancing flow
to multiple boilers.
The installer must ensure that the boiler has adequate flow
without excessive temperature rise. Low system flow can result
in overheating of the boiler water which can cause short burner
cycles, system noise, relief valve discharge and in extreme cases,
a knocking flash to steam. These conditions indicate the need
to increase boiler flow to and from the boiler. This is generally
accomplished by either increasing the size of the boiler pump or
by increasing the diameter of the piping that connects the boiler
to the primary system. A larger diameter pipe reduces head loss
and increases flow.
CAUTION
At no time should the system pressure be less
than 12 PSIG.
CAUTION
Do not allow the flow in the primary loop to
drop lower than the flow in the secondary
loop at any time during boiler operation.
Improper operation of the boiler(s) and
possible tripping of the high limits and relief
valves may occur.
Minimum boiler water temperatures
Inlet water temperatures below the specified minimum of
140°F (60°C) can excessively cool the products of combustion
resulting in condensation on the heat exchanger. Condensation
on the heat exchanger can cause operational problems, bad
combustion, sooting, flue gas spillage and reduced service life
of the related components. See the Low Temperature Bypass
Requirements section for boiler system applications below the
minimum specified temperature.
Low system water volume
System run time is very important to the overall operating
efficiency of the boiler. Short cycling of the boiler creates
problems with condensation in the vent stack, condensation on
the heat exchanger, system temperature spikes, and mechanical
component failures. To prevent short cycling of the boiler, it
is important to limit the boiler cycles to six or fewer per hour.