3 Troubleshooting (continued)
41
FAULT DESCRIPTION CORRECTIVE ACTION
Parameters
Progr
(Will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
SMART SYSTEM
display
to reset.)
After downloading parameters from a laptop,
the main control board must be reset.
Press the ENTER/RESET button on the Smart
System display panel.
Service Blk
While the unit is in Service Mode, the outlet
temperature has exceeded 185°F (85°C).
Establish a heating load to remove heat from the
system.
• Verify that the system is full of water and that all air
has been properly purged from the system.
Verify that the appliance is piped properly into the
system. Refer to the Water Connections Section of
the Installation and Operation Manual for the proper
piping methods.
Check 120 VAC to the pump motor on a call for
heat. If voltage is not present, check the wiring
leading to the main control board. Replace the main
control board if necessary.
If 120 VAC is present on a call for heat and the
pump is not operating, replace the pump.
Low Voltage
120 VAC input to the main control board has
dropped below 100 VAC.
Check 120 VAC supply to the transformer.
Check wiring connections at the low voltage terminal
strip.
Check the wire size/length to remote devices.
Replace the main control board.
Table 3E (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Operator Interface
Copper-fin II/IIE Boiler, Water Heater and Pool Service Manual