2 Venting
The distance of the vent terminal from adjacent
build ings, windows that open and building open ings MUST
comply with the latest edition of the National Fuel Gas
Code, ANSI Z223.1, in Canada, the latest edition of CGA
Standard B149 In stal la tion Code for Gas Burn ing Appliances
and Equipment.
Vent connection is made directly to the top of the
ap pli ance. This appliance is designed with a built-in draft
diverter. No additional external draft hood is re quired. The
connection from the appliance vent to the common vent or
chimney must be made as direct as possible.
A Conventional Negative Draft
Venting System
The negative draft in a conventional vent in stal la tion must be
within the range of a negative 0.02 to 0.05 inches water column
to ensure proper operation. All draft read ings are made while
the appliance is in stable op er a tion (approximately 2 to 5
minutes).
Multiple appliance installations with combined vent ing or
common venting with other negative draft ap pli anc es require
that each appliance must have draft with in the proper range.
If the draft mea sured above the appliance’s built-in draft
diverter ex ceeds the specified range in a dedicated chimney
for a single appliance installation or in combined venting with
other negative draft appliances, a baro met ric damper must be
in stalled to control draft.
Figure 2-1_Conventional Negative Draft Vertical Venting
TABLE - 2A
VENT PIPE SIZES
Input Btu/hr Flue Size
90,000 5"
135,000 6"
180,000 7"
199,000 7"
225,000 7"
270,000 8"
315,000 8"
360,000 9"
399,000 10"
500,000 10"
On a conventionally vented, negative draft ap pli ance, the
connection from the vent to the chimney or vent termination
on the outside of the building MUST be made with listed Type
“B” double wall (or equivalent) vent connectors and must be
direct as possible with no reduction in diameter. To properly
size all double wall vent connectors and stacks, use the venting
tables in the latest edition of the National Fuel Gas Code, ANSI
Z223.1, in Canada, the latest edition of CGA Standard B149
Installation Code for Gas Burning Appliances and Equipment.
The Type “B” vent and accessories, such as firestop spacers,
thim bles, caps, etc., MUST be installed in accordance with the
manufacturer’s list ing. The vent connector and firestop must
provide correct spacing to combustible surfaces and seal to the
vent connector on the upper and lower sides of each floor or
ceiling through which the vent connector passes.
Any vent materials used must be listed by a na tion al ly recognized
test agency for use as vent ma te ri al.