Maintenance
Service Manual
13
Maintenance and annual startup
Table 2A Service and Maintenance Schedules
Service technician
(see the following pages for instructions)
General:
Address reported problems
Inspect interior; clean and vacuum if
necessary
Check for leaks (water, gas, and flue)
Verify flue and air lines in good
condition and sealed tight
Check control settings per the Access
Setup Menu section of this manual
Check ignition and flame sense
electrodes (sand off any deposits;
clean and reposition)
Check wiring and connections
Perform start-up checkout and
performance verification per Section 9
in the EnergyRite Installation and
Operation Manual.
Flame inspection (stable, uniform)
If combustion or performance
indicate need:
Clean burners
Clean heat exchanger
ANNUAL START-UP
Owner maintenance
(see the EnergyRite Users Information Manual for
instructions)
Daily
• Check pool heater area
Monthly
• Check vent piping
Check air inlet piping (if
applicable)
• Check relief valve (if applicable)
Periodically
• Test low water cutoff (if used)
• Reset button (low water cutoff)
Every
6 months
Check pool heater piping (gas
and water) for leaks
Operate relief valve (if
applicable)
End
of season
Shut the pool heater down and
winterize if location is subjected
to freezing temperatures, see the
Winterizing on page 21 of this
manual