Designer’s Guide / Knight XL Boiler
DIRECT VENT / SIDEWALL - CATEGORY IV VENTING
PVC / CPVC WITH CONCENTRIC VENT KITS (400-601 ONLY).
The exhaust piping terminates out the sidewall. The combustion air piping
terminates out the sidewall.
BULLET POINTS
This is Category IV venting, positive pressure,
condensing stack.
All joints and seams must be sealed gastight
and may not be common vented.
The concentric vent termination is provided by
Lochinvar and all other vent material are obtained
locally.
Maximum distance 100 equivalent feet of vent.
Maximum distance 100 equivalent feet of air intake.
Model
Kit Number
Equivalent vent length
KBN 400
CVK3007
5 Feet (1.5 m)
KBN 501
CVK3007
30 Feet (9 m)
KBN 601
CVK3007
30 Feet (9 m)