Designer’s Guide / Knight XL Boiler
DIRECT VENT / SIDEWALL - CATEGORY IV VENTING
PVC / CPVC WITH TWO PIPE TERMINATION.
The exhaust piping terminates out the sidewall. The combustion air piping
terminates out the sidewall.
BULLET POINTS
This is Category IV venting, positive pressure,
condensing stack.
All joints and seams must be sealed gastight
and may not be common vented.
All the vent material for this configuration are
obtained locally, including the terminations.
Maximum distance 100 equivalent feet of vent.
Maximum distance 100 equivalent feet of air intake.