Install Instructions

70
12 Troubleshooting
Combustion Analysis Procedure
1. Shut the water heater down by pressing the UP button for
five (5) seconds.
2. Locate the flue sensor in the vent connection.
Remove the flue sensor and grommet from the unit.
Note: Combustion measurements will be made at this
point.
3. Place the water heater in active position by pressing the
UP button for five (5) seconds.
4. Press ENTER plus the UP button for five (5) seconds to
enter Service Mode.
5. Insert the probe from a combustion analyzer into the
hole left by the removal of the flue temperature sensor.
6. Once the water heater has modulated up to full fire,
measure the combustion. The values should be in the
range listed in Table 12F. The CO levels should be less
than 150 ppm for a properly installed unit.
If the combustion is not within the specified range,
reference the Troubleshooting section of this manual for
possible causes and corrective actions.
7. Once the combustion analysis is complete, exit Service
Mode.
Table 12G Troubleshooting Chart - Combustion Levels
POSSIBLE CAUSE CORRECTIVE ACTION
Vent/Air Intake Length
or Obstruction
Refer to Section 2 - General Venting for the proper venting and air intake methods for the
Shield water heater.
Check for obstructions at the vent/air intake terminals.
Gas Supply Pressure
Refer to Section 7 - Gas Connections for the proper gas supply for the Shield water heater.
Dirty/Damaged Burner
Refer to page 58 of this manual for burner removal and cleaning procedures.
Replace burner if necessary.
Gas Valve Adjustment
Refer to page 71 of this manual for the gas valve adjustment procedure.
Table 12F Flue Products
Natural Gas Propane
CO
2
O
2
CO
2
O
2
8.0% - 10% 3.0% - 6.5% 9.0% - 11% 4.1% - 6.9%
You must replace the flue sensor to prevent
flue gas spillage into the room. Failure
to comply could result in severe personal
injury, death, or substantial property
damage.
WARNING
Installation & Service Manual
8. Replace the flue sensor and grommet into the vent
connection.
9. Place the Shield water heater back into normal operation.