12 Troubleshooting
Table 12E Troubleshooting Chart - Fault Messages Displayed on Water Heater Interface
Installation & Service Manual
ERROR CODE DESCRIPTION CORRECTIVE ACTION
E00
Invalid lockout code.
Reset control module.
• Switch power OFF and ON.
• Replace control module.
E01
The control module has detected parameter
settings that are corrupted.
Replace control module.
E02
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
display to reset.)
The actual fan RPM is more than 30% above
or below the fan speed RPM target.
Vent/air intake lengths exceed the maximum allowed
lengths. Refer to Section 2 - General Venting for
proper lengths.
Check for obstruction or blockage in the vent/air
intake pipes or at terminations.
Check the wiring connections at the fan and at the
main control board.
Replace the fan.
Replace the main control board.
Blown fuse.
Replace fuse F2 on the control board, see page 60
of this manual.
E04
(will require a manual
reset once condition has
been corrected. Press
the RESET button on the
display to reset.)
Either the optional flow switch or the optional
low water cutoff is not making.
Check pump operation on a call for heat.
Check for closed valves or obstructions in the
piping.
Verify system is full of water and all air has been
purged from the system.
Check for loose or misplaced jumpers if flow switch
or LWCO is not installed.
Blown fuse.
• Replace fuse F3 on the control board, see page 60
of this manual.
E05
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
display to reset.)
The flame detector circuit is seeing a flame
signal when the gas valve is closed.
Verify flame is not present. If present, turn off gas
supply and replace gas valve.
Check supply voltage for proper polarity.
Check external wiring for voltage feedback.
Check the flame rod and make sure it is clean.
Check the internal wiring for bad connections.
Replace main control board.