Install Instructions

67
12 Troubleshooting (continued)
Table 12E (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Water Heater
Interface
Installation & Service Manual
ERROR CODE DESCRIPTION CORRECTIVE ACTION
E13
The flue temperature has exceeded 250°F.
Inspect the heat exchanger. Reference page 58 of
this manual for the procedure on how to clean the flue
side of the heat exchanger.
Inspect the flue sensor and associated wiring.
Measure the resistance of the flue sensor and
compare to Table 12C on page 62 of this manual.
Replace the sensor if necessary.
Verify that the vent/air intake pipes are properly
installed and that there are no obstructions.
Replace the main control board.
b05
The flue temperature has exceeded 240°F.
n04
The fan speed is being limited due to the flue
temperature exceeding 215°F.
E15
(will require a manual
reset once the condition
has been corrected.
Press the RESET button
on the
display to reset.)
The outlet water temperature has exceeded
the 210°F manual reset high limit (MRHL)
setting.
Verify that the system is full of water and that all air
has been properly purged from the system.
Verify that the boiler is piped properly into the heating
system. Refer to Section 5 - System Piping
for the proper piping methods for the Shield water
heater.
Check 120 vac to pump motor on a call for
heat. If voltage is not present, check wiring back to
the main control board.
Replace the main control board if necessary.
If 120 vac is present on a call for heat and the boiler
pump is not operating, replace the pump.
If operating on something other than an outlet sensor,
check temperature setting of the main control board.
Check resistance of water sensors and compare to
Table 12B on page 62 of this manual. Replace
sensor if necessary.
b03
The outlet water temperature has exceeded
195°F.
n02
The fan speed is being limited due to the
outlet temperature exceeding 185°F.
E18
(will require a manual
reset once the condition
has been corrected.
Press the RESET button
on the display to reset.)
The control module reads an excessive
temperature difference between the two
outlet sensors.
Check wiring to sensor. Make sure wiring is
connected and not damaged. Reconnect / repair
wiring if necessary.
Measure the resistance of the sensor and compare
to the resistance in Table 12B on page 62 of this
manual. Replace sensor if necessary.
• Replace control module.
E19
(will require a manual
reset once the condition
has been corrected.
Press the RESET button
on the display to reset.)
One or both of the flue sensors is open or
shorted.
Inspect the flue sensor and associated wiring.
Measure the resistance of the flue sensor and
compare to Table 12C on page 62 of this manual.
Replace the sensor if necessary.
Replace the main control board.