12 Troubleshooting
Table 12E (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Water Heater
Interface
Installation & Service Manual
ERROR CODE DESCRIPTION CORRECTIVE ACTION
E21
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
display to reset.)
One or both of the outlet sensors has
opened or shorted.
Check the sensor and its associated wiring. Repair
or replace the sensor or wiring if damaged.
Measure the resistances of the sensors and
compare the resistances to the tables on page 62.
Replace if necessary.
E22
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
display to reset.)
The inlet sensor is open.
Check the sensor and its associated wiring. Repair
or replace the sensor or wiring if damaged.
E23
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
display to reset.)
The inlet sensor is shorted.
b01
The temperature has reached the set point
+ 4°F.
• None
b02
The main control board has received a call
for heat too quickly after the previous call for
heat has ended.
The control board will release the call for heat after
60 seconds.
The control board will release the call for heat if the
outlet temperature drops 10°F.
b04
The temperature rise across the heat
exchanger has exceeded 30°F.
Verify that the system is full of water and that all air
has been properly purged from the system.
Check for 120 vac to the pump motor on a call
for heat. If voltage is not present, check the wiring
on the pump relay back to the main control board.
Replace the main control board if necessary.
If 120 vac is present on a call for heat and the
pump is not operating, replace the pump.
Scale accumulation in the heat exchanger. Verify
that the water chemistry meets the requirements
listed in Section 5 - System Piping.
n03
The fan speed is being limited due to the
temperature rise across the heat exchanger
exceeding 25°F.