Install Instructions

OPEN FRONT
1/4" (6.35 MM)
MINIMUM CLEARANCE
AROUND HOT WATER PIPES
1" (25.4 MM)
MINIMUM CLEARANCE
AROUND VENT PIPE
IMG00463
Figure 1-2 Alcove Installation - Minimum Required Clearances
6"
6"
CLOSED DOOR
VENTILATIING
AIR OPENING
VENTILATIING
AIR OPENING
1/4" (6.35 MM)
MINIMUM CLEARANCE
AROUND HOT WATER PIPES
1" (25.4 MM)
MINIMUM CLEARANCE
AROUND VENT PIPE
IMG00463
A
RE
A
OF E
A
CH O
P
ENING:
1 SQ. INCH PER 1000 BTU PER HOUR INPUT
WITH A MINIMUM OF 100 SQ. INCHES
Figure 1-1 Closet Installation - Minimum Required Clearances
WARNING
9
1 Determine water heater location (continued)
RECOMMENDED SERVICE
CLEARANCES:
Top - 18" (457 mm)
Left/Right Side - 24" (610 mm)
Front - 24" (610 mm)
RECOMMENDED SERVICE
CLEARANCES:
Top - 18" (457 mm)
Left/Right Side - 24" (610 mm)
Front - 24" (610 mm)
Installation & Service Manual
WARNING
For closet installations, CPVC,
polypropylene or stainless steel
vent material MUST BE used in
a closet structure due to elevated
temperatures. Failure to follow
this warning could result in fire,
personal injury, or death.
For alcove installations, CPVC,
polypropylene or stainless steel
vent material MUST BE used
in an alcove structure due to
elevated temperatures. Failure to
follow this warning could result
in fire, personal injury, or death.