Specification Sheet

Important notes
If the hot and dimmed hot feeds to the split
duplex HFDU are supplied from different circuits or
split-wired with separate switch-legs, a means to
simultaneously disconnect these circuits must be
provided at the panel board where they originate
(NEC 210.7(C) 2002 Edition). A 2-pole circuit
breaker or two single-pole circuit breakers with an
approved handle tie can be used to accomplish
this simultaneous disconnect. Feed-through
dimming panels, which are those without breakers,
are recommended when using the HFDU.
Receptacles and plugs for dimming use are
UL listed for use with all Lutron
® wallbox dimmers
included in this catalog.
If there is only one electrical feed to the receptacle,
then the duplex DFDU must be used.
For detailed information, see Application Notes #91
(Guide to Dimming Table Lamps) and #109 (Guide
to Dimming Portable Lamps via Receptacles) at
www.lutron.com/applicationnotes.
120/125 V RP-FDU-10-WH
White
120/125 V RP-FDU-10-BR
Brown
UL/CSA/NOM regulatory approvals.
Replacement plug for dimming
(use with receptacles on left)
This plug required for use with
Lutron
® receptacles for dimming
use—plug will work in standard
receptacle
Easily replaces the existing plugs
on lamps
CC
2
: Gloss color code and Stainless Steel,
see pg. 161
CC
4
: Satin color codes, see pg. 161
*Stainless Steel finish only available as separate
wallplate. Match with separate Black (BL) or
Midnight (MN) controls and accessories.
Wallplates and accessories | Designer | Claro®/Satin Colors®
164A
www.lutron.com | 1.800.523.9466 |