Full Product Manual

Maestro Sensor
369666h 15 02.12.21
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Switch with Occupancy / Vacancy Sensor
Wiring Diagrams (continued)
Wiring Diagram 6 - with Neutral
Multi-Location Installation (277 V~)
1, 2, 3, 4
-OPS6M2-DV, -VPS6M2-DV with MA-AS-277 or MSC-AS-277
Occupancy
sensor switch
3
Black
Blue
White
Ground
Black
Blue
Green
Ground
277 V~
50 / 60 Hz
Black
Blue
Green
Ground
Hot / Live
Neutral
Load
RedRed
Bare
Black
MA-AS-277 or
MSC-AS-277
MA-AS-277 or
MSC-AS-277
Continued on next page...
Wiring Diagram 6 - without Neutral
Multi-Location Installation (277 V~)
1, 2, 3, 4
-OPS6M2-DV, -VPS6M2-DV with MA-AS-277 or MSC-AS-277
Occupancy
sensor switch
3
Black
Blue
Green-
sleeved
wire
Ground
Black
Blue
Green
Ground
277 V~
50 / 60 Hz
Black
Blue
Green
Ground
Hot / Live
Neutral
Load
RedRed
Bare
Black
MA-AS-277 or
MSC-AS-277
MA-AS-277 or
MSC-AS-277
1
A single standard mechanical 3-way switch or up to 9 companion switches may be connected to most occupancy sensor switches.
Standard mechanical 3-way switch cannot be combined with companion switch. Total blue terminal wire length may be up to 150ft (46m).
2
Only one occupancy sensor switch can be used per multi-location circuit.
3
Fan load applies to 120 V~ only (not for 277 V~).
4
Occupancy sensor switch can be installed in any location.
Note: When a neutral connection is available, remove the green sleeve and connect the white wire to neutral.
Note: Connect green-sleeved wire to ground only in retrofit and replacement applications.
15