Owner`s manual

© 2009 Magnum Energy IncPage 30
Installation
2.6 Grounding Inverters
The inverter/charger should always be connected to a permanent, grounded wiring system.
An inverter system that is properly grounded will limit the risk of electrical shock, reduce radio
frequency noise from the inverter and minimize excessive surge voltages induced by lightning.
This is done by ensuring there is a well-de ned, very low-resistance path from the electrical
system to the grounding system. This low-resistance path helps stabilizes the electrical system
voltage with respect to ground and carries fault currents directly to ground if the electrical system
malfunctions.
To understand how the conductors in the electrical circuit will be connected to the system ground,
the following terms should be understood:
Grounded Conductor (GC): The wire/cable in the electrical system that normally carries current (usually
the AC neutral and/or the DC negative); and is intentionally connected or “bonded” to the ground
system. This wire or the ends of this wire should be colored white or gray.
Equipment Grounding Conductor (EGC): A wire/cable that does not normally carry current and is used to
connect the exposed metal parts of equipment - that might be accidentally energized - to the grounding
electrode system or the grounded conductor. This wire or the ends of this wire should be green or green
with a yellow stripe; or this wire can be bare copper.
Grounding Electrode Conductor (GEC): The wire/cable that does not normally carry current and connects
the grounded conductor and/or the equipment grounding conductor to the grounding electrode at the
service equipment.
Grounding Electrode (GE): A ground rod or conducting element that establishes an electrical connection
to the earth.
System bonding jumper (SBJ) The connection between the grounded circuit conductor in the electrical
system and the equipment grounding conductor at a separately derived system.
The MS Series inverter/charger uses both AC and DC power; however the AC electrical system is
isolated from the DC electrical system by an internal transformer. Although this inverter/charger
has two electrical systems, each electrical system must be properly grounded and connected to
a common “earth” reference; refer to gure 2-16.
For proper grounding, each electrical system must connect all exposed metal parts of equipment
(via Equipment Grounding Conductors - EGC) and one of the current-carrying conductors (Grounded
Conductor - GC) together at a common point (Ground Bus-Bar - GBB) usually by a System Bonding
Jumper (SBJ) in an electrical service disconnect panel. The common point of each electrical system
is then connected (via Grounding Electrode Conductor - GEC) to the common ground reference,
such as a ground rod (Grounding Electrode - GE). This connection to earth should only be made
at one point in each electrical system; otherwise, parallel paths will exist for the currents to ow.
These parallel current paths would represent a safety hazard and are not allowed in installations
wired per the NEC/CEC.
Figure 2-16, Grounding System for MS Series
AC
DC Service
Panel
AC Service
Panel
DC Electrical SystemAC Electrical System
Neutral
Positive
Negative
DC
Grounding
System
Negative
SBJ
GC
GE
GEC-AC
EGC
AC Ground DC Ground
SBJ
EGC
GC
Neutral
Hot
GEC-DC
GE
GE
GBB GBB
Grounding Electrode
(AC and DC sides shared)
Grounding Electrode
(DC side dedicated)
Grounding Electrode
(AC side dedicated)
or
or
MS-AE Series Inverter/Charger