2.2 Mounting the Inverter
The inverter base can reach a temperature up to 90°C (194°F) and should be mounted on a
noncombustible surface*. This surface and the mounting hardware must also be capable of
supporting at least twice the weight of the inverter. To meet regulatory requirements, the ME
Series must be mounted in one of the following positions, as shown in Figure 2-2:
above or under a horizontal surface (shelf or table)
or, on a vertical surface (wall) with the DC terminals to the right
or, on a vertical surface (wall) with DC terminals toward the bottom, MP-HOOD (inverter hood)
installed on the top, and either the ME-CB or MPX-CB (conduit box) installed on the inverter’s
bottom.
Info: The ME-CB and MPX-CB enclosures prevent material from falling out the bottom
in the event of an internal re, and also allow suf cient ventilation to prevent the
inverter from overheating under normal operating conditions. The MP-HOOD inverter
hood helps prevent items from falling inside causing damage to the inverter.
After determining the mounting position, refer to the physical dimensions as shown in Figures
2-3 or 2-4, or use the base of the inverter as a template to mark your mounting screw locations.
After marking the mounting screw locations, mount the unit with appropriate mounting hardware.
* Noncombustible surface – A surface made of material that will not ignite, burn, support combustion, or release
ammable vapors when subjected to re or heat as per the ASTM E136 standard. For the most part, these
are materials that are largely comprised of inorganic matter such as stone, steel, iron, brick, tile, concrete,
slate, and glass. Avoid common building materials such as gypsum board, painted surfaces, wall coverings,
and all types of wood. Note: Sensata provides a noncombustible backplate for mounting the inverter.
30
30
SHELF OR TABLE MOUNTED
(UP SIDE DOWN)
SHELF OR TABLE
M
OUNTED
(RIGHT SIDE UP)
WALL MOUNTED
(DC TERMINALS TO THE RIGHT)
WALL MOUNTED
(DC TERMINALS
ON THE BOTTOM*)
*WHEN THE INVERTER
IS MOUNTED IN THIS
POSITION, THE MP-
HOOD (
INVERTER
HOOD ON TOP) AND
THE ME-CB OR
MPX-CB (
CONDUIT
BOX ON BOTTOM) MUST
BE USED.
Figure 2-2, Approved Mounting Positions