Installation Manual

Page 12
© 2015 Sensata Technologies
Installation
2.4 DC Wiring
This section describes the inverter’s required DC wire sizes, the recommended disconnect/
overcurrent protection, and how to make the DC connections to the inverter and the battery bank.
Refer to Figure 2-5 when connecting the DC wires.
WARNING: Even though DC voltage is “low voltage”, signi cant hazards may be
present, particularly from short circuits of the battery system.
CAUTION: The inverter is NOT reverse polarity protected, which means that if the
negative and positive battery voltage is connected backwards to the inverter, the
inverter will likely be damaged. You should verify the correct voltage polarity using
a voltmeter BEFORE connecting the DC wires. Color code the DC cables/wires with
colored tape or heat shrink tubing: RED for positive (+), WHITE for negative (–), and
GREEN (or bare copper) for DC ground to avoid polarity problems.
CAUTION: To remove battery power from the inverter, disconnect the battery positive
connection before the negative connection. This requirement can prevent damage to
the inverter and/or to an accessory connected to the inverter.
Note: When an accessory that is not powered by an inverter (e.g., ME-AGS-N and ME-
BMK) is installed and connected to the inverter (via a network communication cable ),
the battery negative connection of the inverter and each accessory must be at the same
potential (i.e., electrically common with each other) until the positive connection of
each device is removed. This prevents a high impedance path developing between the
connected devices (i.e., inverter and accessories), which can cause the network cable
to become the DC return path to the battery—possibly resulting in permanent damage
to all connected devices on the network. This can be prevented if the battery negative
connection of each device is always connected before connecting/disconnecting any
battery positive.
CAUTION: Before wiring the DC cables, review the safety information at the beginning
of this manual and the instructions below to ensure a safe and long-lived system.
The DC positive and negative cables connected to the inverter from the battery bank should
be tied together with wire ties or electrical tape approximately every 6 inches (153 mm). This
helps improve the surge capability and reduces the effects of inductance, which improves the
inverter waveform and reduces the wear of the inverter’s lter capacitors.
Crimped and sealed copper ring terminal lugs with a 5/16” hole should be used to connect the
DC wires to the inverter’s DC terminals.
The battery bank voltage MUST match the DC voltage required by the inverter (i.e., 12-volt
battery bank for a 12-volt inverter), or the inverter may be damaged.
To ensure the maximum performance from the inverter, all connections from the battery bank
to the inverter should be minimized. The exceptions are the DC overcurrent disconnect in the
positive line, and a shunt in the negative line. Any other additional connection will contribute
to additional voltage drops and these extra connection points may loosen during use.
All wiring to the battery terminals should be checked periodically (once a month) for
proper tightness. The torque requirement for the DC terminals is between 10 to 12 lbf-ft
(13.6 to 16.3 N-m). If you don’t have a torque wrench, ensure all DC terminals are tight and
cannot move.
Be aware that overtightening or misthreading the nuts on the DC terminals can cause the
bolts to strip and snap/break off.
Make sure cables have a smooth bend radius and do not become kinked. Long cable runs
should follow existing wire runs if possible.
A brief spark or arc may occur when connecting the battery cables to the inverter DC terminals;
this is normal and due to the inverter’s internal capacitors being charged.