2.5.8 AC Wiring Con guration (ME2000 models)
The following table provides the different wiring con gurations for installing and connecting the
AC conductors into and out of ME2000 model inverters (see Figures 2-15 and 2-16 for installation
diagrams showing these con gurations).
Table 2-4, AC Input/Output Wiring Con gurations (ME2000 models)
SI/SO (30A)
Single In/
Single Out
SI/DO
Single In/
Dual Out
AC Source
1
Required
120 VAC @ 30A 120 VAC @ 30A
@ 15A/leg
(-15B models);
or, 20A/leg
(-20B models).
Reason to Use Have an 120 VAC
source that is 30A.
Requires a separate
inverter sub-panel.
Do not want to install a
separate inverter sub-
panel.
Inverter pass-thru
capability limited by
model used.
Models ME2000 ME2000-15B
ME2000-20B
Maximum Input
Breaker
Required
Minimum Wire
Size
30A
(single pole)
#12 AWG
(In & Out)
-15B models:
30A (single pole);
-20B models:
30A (single pole)
#12 AWG (In)
#12 AWG x2 (Out)
Maximum
Inverter Pass-
thru capacity
Output
Con gurations
3600W
(30A @ 120 VAC)
3600W (-15B)/
4800W (-20B)
-15B models: 15A/leg
(30A max.);
-20B models: 20A/leg
(30A max.)
Wiring Diagram Figure 2-15 Figure 2-16
Note
1
: AC source is from either utility power or an onboard generator.