Setup
CTRL: 01 ACIn Control
01 ACIn Control menu has four different conditions in which the inverter/charger will connect to
an incoming AC power source. Only one may be selected at any one time—multiple conditions can
be enabled, but only one can be active.
Info: Before the inverter allows the AC input to connect to the AC source (grid or
generator), the incoming AC must be quali ed by the inverter/charger (voltage is
below the high AC input requirements, above the SETUP: 03B VAC Dropout setting, and
between 50 Hz to 70 Hz for domestic models—40 to 60 Hz for export models).
Info: The top line of the LCD display alternates the inverter/charger status with a
secondary AC IN status when AC is present (not connecting as a result of a selection
made in the SETUP menu).
Example: AC is present, but Time Connect has been selected from the 01 ACIn Control
menu and the current time of day is 6PM. The SETUP menu’s 02C AC In - Time current
setting is 2AM-8AM. The current time of 6PM is outside the connect time, so the inverter/
charger will not connect to the incoming AC until after 2AM. The primary status will
display “Inverting” and the secondary status will display “Time Connect” to let you know
the reason that incoming AC has not connected.
• Auto Connect – Automatically connects to incoming AC power when the incoming AC is
quali ed by the inverter/charger (voltage is below the high AC input requirements, above the
SETUP: 03B VAC Dropout setting, and between 50 Hz to 70 Hz for domestic models—40 to
60 Hz for export models).
Info: The Auto Connect setting must be selected if the incoming AC source is a
generator. There is no bene t from using the AC In Control feature if the AC source
is from a generator—the generator power may not be available if an AC In feature is
activated. Also, when the generator is turned on (autostarted or manually), it may be
prevented from connecting because the criteria to allow the AC input to connect (AC In
is based on time, VDC, or SOC) may not have been met.
Note: This is true unless you are using an inverter that has two independent AC inputs—
one for grid and the other for generator (i.e., MSH4024RE)—because the AC In Control
features only work with the GRID IN (AC1) input.
• VDC Connect – Only allows the incoming AC to connect when the DC battery voltage falls be-
low the Connect volts setting in the SETUP menu’s 02D AC In - VDC menu item. Disconnects
from incoming AC when the DC battery voltage rises above the Disconnect volts setting, also
from the 02D AC In - VDC menu. See SETUP menu 02D for more information on the Connect/
Disconnect Volts menu settings.
• Time Connect – Incoming AC only connects when the time of day is between the Connect
and Disconnect time settings in the SETUP menu’s 02C AC In - Time menu item. See SETUP
menu 02C for more information on the Set Connect/Disconnect time menu settings.
• SOC Connect – Incoming AC only connects when the battery bank State of Charge (SOC)
falls below the Connect SOC setting in the SETUP menu’s 02E AC In - SOC menu item. Discon-
nects from incoming AC when the battery bank SOC rises above the Disconnect SOC setting,
also from the 02E AC In - SOC menu. This feature requires the optional ME-BMK (battery
monitor) to be installed. See SETUP menu 02E for more information on the Set Connect SOC
menu settings.
ACIn - Disabled – Disconnects incoming AC when selected. This setting will prevent incom-
ing AC from connecting to the inverter/charger.