Installation Manual

Page 42
© 2014 Magnum Energy, Inc.
Menu Maps
SETUP
[Status/Fault]
03 Charger Setup
continued….
SETUP button menu map continues on next page
03B VAC Dropout
80 VAC
03C Battery Type
Flooded
Set VAC Dropout
80 VAC
Set Battery Type
Flooded
Set VAC Dropout
AC1 = 80 VAC
Set VAC Dropout
AC2 = 70 VAC
Note: Shading denotes screens that
display with MSH-RE models only
Set CV Chg Done
Time = 2.0 Hrs
Set Max Charge
Amps = 200 ADC
Set Max CC/CV
Time = 12.0 Hrs
P
R
R
P
R
R
R
5A - 60A
Set AC1 Input
Amps = 30A
Set AC2 Input
Amps = 20A
P
R
R
Set AC Input
Amps = 30A
5A - 60A
R
R
R
03A AC Input
Amps = 30A
03A AC Input
Amps = 30A / 20A
P
P
P
03B VAC Dropout
80 VAC / 70 VAC
P
P
P
R
60-100 VAC,UPS Mode
60-100VAC
60-100VAC,UPS Mode
GEL, AGM1,
AGM2,
Custom, CC/CV
R
5A - 60A
Set Float
Volts = 13.2
Set Absorb
Volts = 14.4
Set EQ Done
Time = 4.0 Hrs
Set EQ
Volts = 15.6
P
P
R
R
R
12.0 – 16.0 VDC
12.0 – 16.0 VDC
12.0 – 16.0 VDC 0.1 – 25.5 Hrs
R
P
PP
Set CV Charge
Volts = 13.8
P
Set CV Chg Done
Time
P
R
OFF, 20-990 ADC
R
R
Hold CV Chg VDC
Amps
Set Recharge
Volts = 12.0
Set CV Chg Done
Amps
= 20 ADC
P
P
12.0-16.0 VDC
0-250 ADC
0.1-25.5 Hrs
R
R
OFF, 0.1-25.5 Hrs
12.0-16.0 VDC
P
R
Figure 4-3, SETUP Button Menu Map