Installation Manual

© 2014 Magnum Energy, Inc.Page 87
Using an AGS Module: Troubleshooting
Remedy: Con rm that all the autostop parameters that are active or enabled can be
satis ed before the SETUP: 04F Max Gen Run Time setting is reached.
If using the SETUP: 04A Gen Run VDC menu’s parameters with:
a battery voltage setting to autostop – ensure the autostop voltage is less than the
temperature-compensated absorb charge voltage.
the Float setting to autostop – ensure the time that the charger is in the Bulk Charge
and Absorb Charge¹ stages is shorter than the 04F Max Gen Run Time setting.
Refer to the SETUP: 04A Gen Run VDC section for additional information on this setting.
• If using SETUP: 04B Gen Run Time, con rm you have not set the total run time
(start time to the stop time) longer than the SETUP: 04F Max Gen Run Time setting.
• If using SETUP: 04C Gen Run Amps, con rm the inverter load(s) that is used to de-
termine the Stop Gen AC Amps setting is not required to run longer than the SETUP:
04F Max Gen Run Time setting.
• If using SETUP: 04D Gen Run SOC, con rm that the METER: 05B Battery SOC read-
ing is not “Think’n”, but shows an actual percentage reading on the display (i.e.,
85%), and the Stop Gen SOC setting can be satis ed before the SETUP: 04F Max
Gen Run Time setting is reached.
• If using SETUP: 04E Gen Run Temp, the temperature around the remote tempera-
ture sensor has not reached the Gen Run Temp setting. You need to either lower the
Gen Run Temp Start setting, determine how to cool the area (remote temp sensor
location) to below the Gen Run Temp Start setting before the 04F Max Gen Run Time
setting is reached, or increase the Max Gen Run Time setting.
Lastly, con rm that your warm-up and/or cooldown time when added to your autostop
condition does not exceed the SETUP: 04F Max Gen Run Time setting.
Info: Beginning with Version 5.2 of the ME-AGS-N, the Max Gen Run Time setting
can be defeated. In some cases, it may be appropriate to set the Max Gen Run Time
setting to OFF. However, this feature is mainly provided as a safety feature to ensure
the generator doesn’t run longer than the time it takes to reach the autostop conditions
or to expend the generator’s fuel capacity, whichever occurs rst – take this into
consideration if this setting is defeated.
Note¹: Several conditions determine the length of time that the charger is in the Absorb Charge
stage. Ensure the SETUP: 03D Absorb Done (Time, Amps, or SOC) setting—determines when the
Absorb Charge stage is complete and enters the Float stage—is taken into account when setting
the 04F Max Gen Run Time setting.
7.3.4 How to Clear AGS Faults
Go to the CTRL: 03 Gen Control menu, and then select OFF.
Note: After the fault clears and the reason for the fault is determined, be sure to re-enable the
AGS to autostart. Go to the CTRL: 03 Gen Control menu and select AUTO. Refer to Figure 7-2.
Once the fault is cleared and the reason for the fault is determined, you should re-enable the AGS
to see if the fault returns, or test the AGS/generator system by performing the AGS functional
test for your remote (see Section 7.1.2).
7.3.5 How to Clear AGS Fault History
Go to the TECH: 04 Fault History menu, press the SELECT knob, and then turn the knob until the
04D Clear Faults screen appears.
At the 04D Clear Faults screen, press and hold the SELECT knob until the “5.0 to 0.0 second
screen countdown is nished and the screen displays “HISTORY CLEARED”.
CAUTION: Before using the Clear Faults feature, be sure you do not want the fault
history for any device (inverter, AGS, or PT controller). Once fault history data has been
cleared, it cannot be retrieved.