Installation Manual

© 2010 Magnum Energy, Inc.
Internal Fault - The inverter continually monitors several inter-
nal components and the processor communications. If a condition
occurs that doesn’t allow proper internal operation, the inverter
will shut down to protect itself and the connected loads. The
inverter will need to be reset to start operating.
Table 5, Inverter Battery Turn On/Off Levels
* - adjustable with remote
Inverter Startup
ON/OFF Switch - The inverter can be turned on and off by lightly
pressing and releasing the Power ON/OFF switch on the front of the
inverter. When the inverter is rst connected to the batteries, or when
its automatic protection circuit has turned the inverter off, the ON/OFF
switch will need to be pressed to start the unit. Once the inverter
has been turned on, pressing the Power ON/OFF switch alternately
turns the inverter on and off.
WARNING: The Power ON/OFF control switch does not
turn on or off the charger feature. If AC power (utility or
generator) is connected and quali ed on the AC input,
this AC power will also be available on the AC output
and is not controlled by the Power ON/OFF switch.
Status LED Indicator - The status indicator is a green LED (Light
Emitting Diode) that provides information on the operational mode of
the inverter. Watch this indicator for at least 10 seconds to determine
the inverter’s operational condition from the information below:
Inverter Mode
Off - Indicates the inverter is off; there is no AC power from
the inverter, utility, or generator at the inverter’s output
terminals.
Blinks On (once every second) - The inverter is on and is
using energy from the battery. The inverter is either provid-
ing full power to the loads connected to the inverter, or it’s in
Search Mode and ready to supply AC power to the connected
loads.
3.0 Operation
29
Inverter Battery
Turn On/Off
Levels
Inverter Model
MM612AE MM1512AE MM1524AE
HBCO >15.8 VDC >15.8 VDC >31.6 VDC
HBCI 15.5 VDC 15.5 VDC 31.0 VDC
LBCI 12.5 VDC 12.5 VDC 25.0 VDC
LBCO*
(one minute delay)
10.0 VDC
(9.0 - 12.2 VDC
)
10.0 VDC
(9.0 - 12.2 VDC
)
20.0 VDC
(18.0 - 24.4 VDC)
LBCO
(immediate)
8.5 VDC 8.5 VDC 17.0 VDC