4.0 Maintenance and Troubleshooting
4.0 Maintenance and Troubleshooting
Recommended Inverter and Battery Care
The MM-AE Series inverter/charger is designed to provide you with
years of trouble-free service. Even though there are no user-service-
able parts, it is recommended that every 6 months you perform the
following maintenance steps to ensure optimum performance and
extend the life of your batteries.
WARNING: Prior to performing these checks, switch
both the AC and DC circuits OFF.
Visually inspect the batteries for cracks, leaks, or swelling –
replace if necessary.
Use baking soda to clean and remove any electrolyte spills or
buildups.
Check and tighten all battery holddown clamps.
Clean and tighten (10 to 12 foot-pounds) all DC terminals
(battery and inverter) and connecting cables.
Check and ll battery water levels (Liquid Lead Acid batteries
only).
Check individual battery voltages (replace those that vary
more than 0.3 VDC of each other).
Check all cable runs for signs of cha ng – replace if necessary.
Check the inverter’s cooling vents – clean as necessary.
Resetting the Inverter
Under some fault conditions (i.e., an internal fault), the inverter will
need to be reset.
To reset the inverter:
Press and hold the Power ON/OFF pushbutton for approximately
15 seconds, or until the status LED comes on and ashes rapidly
(see Figure 2, Items 1 and 2).
Release the Power ON/OFF pushbutton once the rapid ashing
has begun. The status LED will go off.
Press the Power ON/OFF pushbutton again to turn the
inverter on.
Info: The Power ON/OFF pushbutton is a small momentary
type switch which operates by lightly pressing and
releasing.