Operating instructions

156 720 607 160
Measure
40mm
Top
View
Wall
Rear
Flue
Side
Flue
10mm
Wall
Thickness
Drip Ring
10mm
Fig. 14
12.3.1 Standard Telescopic Flue Installation:
Determine appropriate flue length (Fig. 14)
Rear Flue Application - Measure wall thickness, add 60mm.
Side flue application – Measure distance from outer face
of wall to centre line of appliance, deduct 55mm.
Set the Telescopic flue tubes to the length determined.
Drill through the pilot hole in the outer duct and secure with
the self tapping screw provided. Wrap tape around joint on
the outer duct to seal the flue, slide the drip ring in position
to coincide with the wall cavity.
Slide flue through the hole in wall until it stops against the
bayonet pin.
For side flue Applications – re orient flue support ring on
top of appliance: (Fig. 15) Unfasten Flue Support Ring (x 4
screws). Turn ring 90 degrees to left or right as appropriate.
Re secure.
Position the white painted Flue Elbow onto the Flue Support
Ring ensuring the Silicone Seal engages over the Fan Outlet,
secure the Elbow with 3 off screws provided.
Slide the Flue forward from the wall until it engages in the
white painted elbow’s bayonet connection, twist
anticlockwise to lock. (Fig. 16)
Drill through the pilot hole in the white flue elbow and lock
the flue in position with self tapping screw provided.
Make good the opening around the flue.
12.3.2Extended Horizontal Flue Installation:
The flue may be extended to the maximum configuration
lengths shown in Table 8 with the application of 1m extension
kits, 45 and 90 degree Elbows and a Telescopic Flue In
Line Elbow Adapter. In all configurations the first section of
Standard Horizontal Flue is located in the white painted
Flue Elbow, the second section terminates the flue after the
extension components.
The 1m extensions can be cut to length as required.
Extended Horizontal flue with direct vertical rise:
The flue may be extended with a direct vertical rise from the
appliance with the application of a Vertical Flue Adapter,
1m extension kits, 90 degree elbow and a telescopic flue in
line elbow adapter. The maximum flue length for this
configuration is as per table 8.
Fig. 15
Flue
Elbow
Flue
Elbow
Connect
Flue
Lock Flue
into
position
Drill and screw
elbow and flue
The Flue Elbow
Arrow MUST align
to Flue Pin as shown
Fig. 16
Table 8
Flue length Restricto
r
Configuration
A
White flue elbow only –
no additional bends
4.0 m Max Table 6
Configuration
B
White Flue Elbow +
1 x 90 degree bend
2.2 m Max
None
required
Configuration
C
White Flue Elbow +
2x 45 degree bends
2.5 m Max
None
required
Configuration
D
White Flue Elbow +
2x 90 degree bends
1.8 m Max
None
required
Configuration
E
Direct vertical rise from the
appliance: Vertical Adapter
+ 1 x 90 degree bend
3.5 m Max Table 6
Horizontal configuration
Minimum flue length:
Rear flue, 230mm wall thickness.
0.29 m Min