Specifications

Diagram shows typical charging method.
26
Note : R407C - Fix filter dryer
R22 - Nil
R410A - Nil
(6) Additional Charge
The refrigerant charge has already charged into the outdoor unit. For the piping length of 7.6m, additional
refrigerant charge after vacuuming is not necessary.
When the piping length is more than 7.6m, please use the table below (unit in gram).
R22
R410A
The additional refrigerant charge amount recommended is a guideline for longer piping application. The actual
charge required may be different from the guideline due to different application and variation in site conditions.
Model 10m 12m 15m 25m 35m 45m
018C/CR 38 / 54 69 / 98 116 / 166 - - -
020C/CR 37 / 38 69 / 69 115 / 116 - - -
025C/CR 95 / 132 173 / 243 292 / 408 - - -
028C/CR 94 / 133 173 / 244 291 / 411 - - -
030C/CR 133 / 133 243 / 243 409 / 409 962 / 961 1515 / 1514 2068 / 2067
035C/CR 130 / 136 238 / 248 400 / 418 940 / 983 1481 / 1547 2021 / 2112
040C/CR 134 / 136 245 / 248 412 / 418 968 / 983 1525 / 1547 2081 / 2112
050C/CR 130 / 134 238 / 245 400 / 412 942 / 968 1483 / 1525 2024 / 2081
061C/CR 245 / 243 450 / 446 756 / 751 1778 / 1765 2799 / 2780 -
Model 10m 12m 15m 25m 35m 45m
035C/CR 63 / 100 116 / 182 195 / 307 457 / 721 720 / 1136 983 / 1551
040C/CR 61 / 97 112 / 178 189 / 299 445 / 703 700 / 1107 956 / 1511
050C/CR 50 / 87 92 / 159 155 / 267 363 / 628 572 / 989 781 / 1350
061C/CR 94 / 163 173 / 298 290 / 502 682 / 1179 1075 / 1857 -