Specifications

65
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
Safety Devices
M5LC 035C M5LC 040C
NC NC
OPEN kPa / psi
2937 / 426 2937 / 426
CLOSE kPa / psi
2413 / 350 2413 / 350
NC NC
OPEN kPa / psi
124 / 18 124 / 18
CLOSE kPa / psi
193 / 28 193 / 28
N/A / <YES> N/A / <YES>
DISCHARGE THERMOSTAT SETTING - 1Ø / <3Ø>
°C / °F
N/A / <130 / 266> N/A / <130 / 266>
M5CM 050D M5CM 062C
M5LC 050C M5LC 061C
NC NC
OPEN kPa / psi
2937 / 426 2937 / 426
CLOSE kPa / psi
2413 / 350 2413 / 350
NC NC
OPEN kPa / psi
124 / 18 124 / 18
CLOSE kPa / psi
193 / 28 193 / 28
YES YES
DISCHARGE THERMOSTAT SETTING °C / °F
130 / 266 130 / 266
M5LC 035CR M5LC 040CR
NC NC
OPEN kPa / psi
2937 / 426 2937 / 426
CLOSE kPa / psi
2413 / 350 2413 / 350
N/A N/A
OPEN kPa / psi
N/A N/A
CLOSE kPa / psi
N/A N/A
N/A / <YES> N/A / <YES>
DISCHARGE THERMOSTAT SETTING - 1Ø / <3Ø>
°C / °F
N/A / <130 / 266> N/A / <130 / 266>
M5CM 050DR M5CM 062CR
M5LC 050CR M5LC 061CR
NC NC
OPEN kPa / psi
2937 / 426 2937 / 426
CLOSE kPa / psi
2413 / 350 2413 / 350
N/A N/A
OPEN kPa / psi
N/A N/A
CLOSE kPa / psi
N/A N/A
YES YES
DISCHARGE THERMOSTAT SETTING °C / °F
130 / 266 130 / 266
MODEL
INDOOR UNIT
OUTDOOR UNIT
PHASE SEQUENCER - 1Ø / <3Ø>
SAFETY DEVICE
HIGH PRESSURE SWITCH
TYPE
LOW PRESSURE SWITCH
TYPE
SAFETY DEVICE
HIGH PRESSURE SWITCH
TYPE
LOW PRESSURE SWITCH
TYPE
PHASE SEQUENCER
MODEL
INDOOR UNIT M5CM 040D
OUTDOOR UNIT
INDOOR UNIT M5CM 040DR
OUTDOOR UNIT
PHASE SEQUENCER
MODEL
INDOOR UNIT
OUTDOOR UNIT
MODEL
SAFETY DEVICE
HIGH PRESSURE SWITCH
TYPE
LOW PRESSURE SWITCH
TYPE
PHASE SEQUENCER - 1Ø / <3Ø>
SAFETY DEVICE
HIGH PRESSURE SWITCH
TYPE
LOW PRESSURE SWITCH
TYPE