Specifications

69
3
rd
Step:
To obtain the Total capacity and Sensible capacity for
(a) Indoor Condition: 23°C DB, 15°C WB
Outdoor Condition: 37°C DB
Total capacity, TC
Interpolation Method:
x = 4.725kW
Sensible capacity, SC
Interpolation Method:
y = 3.214kW
40°C - 35°C
=
4.485kW - 4.885kW
40°C - 37°C 4.485kW - x
40°C - 35°C
=
2.965kW - 3.380kW
40°C - 37°C 2.965kW - y
Outdoor DB ° C
Indoor DB Indoor WB 35 37 40
° C ° C TC (kW) SC (kW) TC (kW) SC (kW) TC (kW) SC (kW)
23 15 4.885 3.380 xy4.485 2.965