Specifications

14
Performance Table
R22 MODELS
(COOLING ONLY)
MODEL : MWM 007F / MLC 007B
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C kW 19.4 25 30 35 40 46
26.7 13.9 TC
2.525 2.331 2.157 1.984 1.810 1.602
SC
2.525 2.331 2.157 1.984 1.810 1.602
15 TC
2.594 2.395 2.217 2.038 1.860 1.646
SC
2.413 2.243 2.090 1.938 1.786 1.603
18 TC
2.784 2.570 2.378 2.187 1.996 1.767
SC
2.110 2.003 1.908 1.813 1.718 1.604
19.4 TC
2.872 2.651 2.454 2.257 2.060 1.823
SC
1.968 1.891 1.823 1.755 1.686 1.604
20 TC
2.910 2.691 2.497 2.302 2.107 1.873
SC
1.907 1.832 1.765 1.698 1.630 1.550
22 TC
3.036 2.826 2.639 2.451 2.264 2.039
SC
1.705 1.634 1.571 1.507 1.444 1.368
24 TC
3.162 2.961 2.781 2.601 2.421 2.205
SC
1.502 1.436 1.376 1.317 1.257 1.186
MODEL : MWM 010F / MLC 010B
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C kW 19.4 25 30 35 40 46
26.7 13.9 TC
2.758 2.602 2.463 2.324 2.185 2.018
SC
2.758 2.602 2.463 2.324 2.185 2.018
15 TC
2.904 2.733 2.581 2.428 2.276 2.092
SC
2.565 2.439 2.327 2.215 2.103 1.968
18 TC
3.302 3.090 2.900 2.711 2.522 2.294
SC
2.039 1.995 1.956 1.917 1.878 1.831
19.4 TC
3.487 3.256 3.049 2.843 2.636 2.389
SC
1.794 1.788 1.783 1.778 1.773 1.768
20 TC
3.567 3.329 3.117 2.906 2.694 2.439
SC
1.688 1.689 1.691 1.692 1.693 1.694
22 TC
3.832 3.574 3.344 3.114 2.884 2.608
SC
1.338 1.361 1.382 1.402 1.423 1.448
24 TC
4.097 3.819 3.571 3.323 3.075 2.778
SC
0.987 1.032 1.073 1.113 1.154 1.202
MODEL : MWM 015F / MLC 015B
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C kW 19.4 25 30 35 40 46
26.7 13.9 TC
3.192 3.076 2.973 2.870 2.767 2.643
SC
3.073 2.983 2.902 2.821 2.740 2.643
15 TC
3.522 3.349 3.195 3.040 2.886 2.700
SC
2.994 2.898 2.812 2.726 2.640 2.536
18 TC
4.424 4.094 3.800 3.505 3.211 2.857
SC
2.779 2.666 2.566 2.466 2.366 2.246
19.4 TC
4.844 4.442 4.082 3.722 3.362 2.931
SC
2.678 2.558 2.452 2.345 2.238 2.110
20 TC
5.025 4.603 4.227 3.851 3.474 3.023
SC
2.635 2.510 2.398 2.287 2.175 2.042
22 TC
5.626 5.142 4.711 4.279 3.848 3.330
SC
2.491 2.348 2.221 2.094 1.966 1.813
24 TC
6.227 5.681 5.195 4.708 4.221 3.637
SC
2.347 2.187 2.044 1.900 1.757 1.585
All the data above are based on 26.7°C entering DB. To obtain data for different entering DB, please use the formula below :
Sensible capacity (@EDB) = Sensible capacity (@26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
Where, BPF = Bypass factor
EDB = Entering dry bulb temperature, ° C
MWM 007F MWM 010F MWM 015F
MLC 007B MLC 010B MLC 015B
Bypass Factor
0.30 0.27 0.34