Specifications

15
MODEL : MWM 020F / MLC 020B
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C kW 19.4 25 30 35 40 46 50 52 54
26.7 13.9 TC
5.161 4.907 4.680 4.453 4.030 3.738 3.597 3.542 3.498
SC
4.729 4.565 4.420 4.274 3.868 3.588 3.452 3.400 3.357
15 TC
5.399 5.139 4.908 4.676 4.232 3.925 3.777 3.719 3.673
SC
4.479 4.350 4.234 4.119 3.728 3.458 3.327 3.276 3.236
18 TC
6.047 5.774 5.529 5.285 4.783 4.436 4.268 4.203 4.151
SC
3.797 3.761 3.728 3.696 3.345 3.103 2.985 2.940 2.903
19.4 TC
6.350 6.069 5.819 5.569 5.040 4.674 4.498 4.429 4.374
SC
3.479 3.486 3.492 3.499 3.167 2.937 2.826 2.783 2.748
20 TC
6.480 6.183 5.919 5.655 5.118 4.747 4.567 4.498 4.442
SC
3.343 3.347 3.351 3.355 3.036 2.816 2.709 2.668 2.635
22 TC
6.912 6.563 6.252 5.941 5.377 4.987 4.799 4.726 4.667
SC
2.889 2.884 2.879 2.874 2.601 2.413 2.321 2.286 2.258
24 TC
7.344 6.943 6.586 6.228 5.637 5.228 5.030 4.954 4.892
SC
2.434 2.420 2.407 2.394 2.166 2.009 1.933 1.904 1.880
HIGH AMBIENT
MODEL : MWM 025F / MLC 025B
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C kW 19.4 25 30 35 40 46 50 52 54
26.7 13.9 TC
5.970 5.765 5.581 5.398 5.231 4.966 4.838 4.789 4.750
SC
5.692 5.545 5.414 5.283 5.120 4.860 4.735 4.687 4.649
15 TC
6.605 6.289 6.007 5.725 5.549 5.267 5.131 5.079 5.038
SC
5.492 5.336 5.196 5.057 4.901 4.652 4.532 4.486 4.450
18 TC
8.337 7.720 7.169 6.617 6.414 6.088 5.931 5.871 5.824
SC
4.947 4.765 4.602 4.440 4.303 4.084 3.979 3.939 3.907
19.4 TC
9.145 8.388 7.711 7.034 6.817 6.471 6.305 6.241 6.190
SC
4.692 4.498 4.325 4.152 4.024 3.819 3.721 3.684 3.654
20 TC
9.492 8.697 7.988 7.279 7.055 6.696 6.524 6.458 6.405
SC
4.583 4.385 4.209 4.033 3.909 3.710 3.615 3.578 3.549
22 TC
10.647 9.730 8.913 8.095 7.845 7.447 7.255 7.182 7.123
SC
4.219 4.010 3.823 3.636 3.525 3.345 3.260 3.227 3.200
24 TC
11.801 10.764 9.837 8.911 8.636 8.197 7.987 7.906 7.841
SC
3.855 3.634 3.437 3.240 3.141 2.981 2.904 2.875 2.852
HIGH AMBIENT
MODEL : MWM 031F / MLC 031B
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C kW 19.4 25 30 35 40 46 50 52 54
26.7 13.9 TC
6.887 6.620 6.382 6.143 5.849 5.541 5.302 5.172 5.035
SC
6.628 6.415 6.225 6.036 5.746 5.541 5.209 5.081 4.947
15 TC
7.525 7.156 6.827 6.497 6.186 5.861 5.607 5.470 5.325
SC
6.471 6.262 6.076 5.889 5.556 5.264 5.037 4.913 4.783
18 TC
9.263 8.617 8.040 7.463 7.105 6.731 6.441 6.283 6.116
SC
6.043 5.844 5.666 5.489 5.037 4.773 4.566 4.455 4.337
19.4 TC
10.075 9.299 8.606 7.913 7.534 7.138 6.830 6.662 6.486
SC
5.844 5.649 5.476 5.302 4.795 4.543 4.347 4.240 4.128
20 TC
10.422 9.610 8.885 8.160 7.768 7.360 7.042 6.870 6.688
SC
5.758 5.545 5.355 5.164 4.624 4.381 4.192 4.089 3.981
22 TC
11.581 10.648 9.815 8.981 8.551 8.101 7.751 7.561 7.361
SC
5.473 5.198 4.952 4.706 4.052 3.839 3.673 3.583 3.488
24 TC
12.740 11.686 10.744 9.803 9.333 8.842 8.460 8.253 8.034
SC
5.188 4.851 4.549 4.247 3.480 3.297 3.155 3.078 2.996
HIGH AMBIENT
All the data above are based on 26.7°C entering DB. To obtain data for different entering DB, please use the formula below :
Sensible capacity (EDB) = Sensible capacity (26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
Where, BPF = Bypass factor
EDB = Entering dry bulb temperature, ° C
MWM 020F MWM 025F MWM 031F
MLC 020B MLC 025B MLC 031B
Bypass Factor
0.35 0.36 0.38