Specifications

16
MODEL : MWM 031F / MLC 031C
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C kW 19.4 25 30 35 40 46 50 52 54
26.7 13.9 TC
8.060 7.677 7.336 6.994 6.659 6.309 6.036 5.888 5.732
SC
7.613 7.325 7.067 6.809 6.483 6.142 5.877 5.733 5.581
15 TC
8.539 8.113 7.734 7.354 7.001 6.633 6.347 6.191 6.027
SC
7.299 7.038 6.806 6.573 6.204 5.878 5.624 5.486 5.341
18 TC
9.845 9.303 8.819 8.335 7.935 7.518 7.193 7.017 6.831
SC
6.443 6.258 6.093 5.928 5.444 5.158 4.935 4.814 4.687
19.4 TC
10.455 9.858 9.325 8.792 8.371 7.931 7.588 7.402 7.206
SC
6.044 5.894 5.761 5.627 5.090 4.822 4.614 4.501 4.382
20 TC
10.716 10.091 9.533 8.975 8.544 8.095 7.746 7.556 7.356
SC
5.872 5.717 5.578 5.440 4.868 4.612 4.413 4.304 4.190
22 TC
11.587 10.868 10.225 9.582 9.123 8.643 8.270 8.067 7.854
SC
5.302 5.126 4.970 4.814 4.128 3.911 3.742 3.650 3.554
24 TC
12.458 11.644 10.917 10.190 9.701 9.191 8.794 8.579 8.352
SC
4.731 4.536 4.362 4.187 3.388 3.210 3.071 2.996 2.917
HIGH AMBIENT
All the data above are based on 26.7°C entering DB. To obtain data for different entering DB, please use the formula below :
Sensible capacity (EDB) = Sensible capacity (26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
Where, BPF = Bypass factor
EDB = Entering dry bulb temperature, ° C
MWM 031F
MLC 031C
Bypass Factor
0.32