MODEL : MWM 007F / MLC 007C
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C kW 19.4 25 30 35 40 46
26.7 13.9 TC
2.580 2.357 2.157 1.958 1.758 1.519
SC
2.580 2.357 2.157 1.958 1.758 1.519
15 TC
2.600 2.383 2.188 1.994 1.800 1.567
SC
2.416 2.231 2.065 1.900 1.734 1.535
18 TC
2.654 2.453 2.273 2.093 1.913 1.698
SC
1.970 1.888 1.815 1.741 1.668 1.580
19.4 TC
2.680 2.486 2.313 2.140 1.966 1.758
SC
1.762 1.728 1.698 1.667 1.637 1.600
20 TC
2.691 2.504 2.336 2.169 2.002 1.802
SC
1.673 1.645 1.619 1.594 1.569 1.539
22 TC
2.727 2.563 2.416 2.269 2.122 1.946
SC
1.376 1.367 1.359 1.350 1.342 1.333
24 TC
2.763 2.622 2.495 2.369 2.242 2.090
SC
1.078 1.089 1.098 1.107 1.116 1.127
MODEL : MWM 010F / MLC 010C
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C kW 19.4 25 30 35 40 46
26.7 13.9 TC
2.859 2.682 2.524 2.366 2.208 2.018
SC
2.859 2.682 2.524 2.366 2.208 2.018
15 TC
3.005 2.810 2.636 2.461 2.287 2.078
SC
2.702 2.547 2.409 2.271 2.133 1.967
18 TC
3.405 3.159 2.940 2.721 2.503 2.240
SC
2.276 2.181 2.096 2.012 1.927 1.826
19.4 TC
3.591 3.322 3.083 2.843 2.603 2.315
SC
2.076 2.010 1.950 1.891 1.831 1.760
20 TC
3.671 3.398 3.155 2.911 2.668 2.376
SC
1.991 1.929 1.874 1.819 1.763 1.697
22 TC
3.937 3.651 3.395 3.139 2.884 2.577
SC
1.707 1.661 1.619 1.578 1.537 1.487
24 TC
4.204 3.903 3.635 3.367 3.099 2.778
SC
1.422 1.392 1.365 1.338 1.311 1.278
MODEL : MWM 015F / MLC 015C
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C kW 19.4 25 30 35 40 46
26.7 13.9 TC
3.400 3.210 3.040 2.870 2.701 2.497
SC
3.142 3.006 2.885 2.764 2.643 2.497
15 TC
3.548 3.351 3.175 3.000 2.824 2.613
SC
2.971 2.854 2.750 2.645 2.541 2.416
18 TC
3.952 3.737 3.545 3.352 3.160 2.930
SC
2.502 2.438 2.380 2.322 2.265 2.196
19.4 TC
4.140 3.917 3.717 3.517 3.317 3.077
SC
2.284 2.243 2.208 2.172 2.136 2.093
20 TC
4.221 3.990 3.784 3.578 3.372 3.124
SC
2.190 2.152 2.119 2.085 2.051 2.011
22 TC
4.491 4.236 4.008 3.781 3.553 3.280
SC
1.878 1.849 1.823 1.797 1.771 1.740
24 TC
4.760 4.481 4.232 3.984 3.735 3.436
SC
1.565 1.545 1.527 1.508 1.490 1.468
All the data above are based on 26.7°C entering DB. To obtain data for different entering DB, please use the formula below :
Sensible capacity (@EDB) = Sensible capacity (@26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
Where, BPF = Bypass factor
EDB = Entering dry bulb temperature, ° C
MWM 007F MWM 010F MWM 015F
MLC 007C MLC 010C MLC 015C
Bypass Factor
0.28 0.29 0.32