21
MODEL : MWM 007FR / MLC 007CR
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C kW 19.4 25 30 35 40 46
26.7 13.9 TC
2.492 2.305 2.137 1.970 1.803 1.602
SC
2.492 2.305 2.137 1.970 1.803 1.602
15 TC
2.533 2.352 2.190 2.027 1.865 1.671
SC
2.351 2.199 2.064 1.929 1.794 1.632
18 TC
2.646 2.480 2.332 2.184 2.036 1.858
SC
1.965 1.912 1.865 1.817 1.770 1.713
19.4 TC
2.699 2.540 2.398 2.257 2.115 1.945
SC
1.785 1.778 1.772 1.765 1.758 1.751
20 TC
2.721 2.565 2.425 2.286 2.146 1.979
SC
1.708 1.702 1.696 1.690 1.685 1.678
22 TC
2.796 2.648 2.516 2.383 2.251 2.092
SC
1.451 1.448 1.445 1.442 1.439 1.436
24 TC
2.872 2.731 2.606 2.481 2.355 2.205
SC
1.195 1.194 1.194 1.194 1.193 1.193
MODEL : MWM 010FR / MLC 010CR
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C kW 19.4 25 30 35 40 46
26.7 13.9 TC
2.881 2.691 2.521 2.351 2.181 1.977
SC
2.881 2.691 2.521 2.351 2.181 1.977
15 TC
3.028 2.816 2.627 2.437 2.248 2.021
SC
2.728 2.564 2.418 2.272 2.126 1.951
18 TC
3.429 3.158 2.916 2.674 2.432 2.142
SC
2.311 2.220 2.139 2.058 1.977 1.880
19.4 TC
3.616 3.317 3.051 2.784 2.518 2.198
SC
2.116 2.059 2.009 1.958 1.907 1.846
20 TC
3.696 3.395 3.126 2.857 2.589 2.266
SC
2.033 1.979 1.931 1.883 1.836 1.778
22 TC
3.963 3.653 3.377 3.101 2.825 2.493
SC
1.755 1.712 1.673 1.635 1.597 1.551
24 TC
4.230 3.912 3.628 3.345 3.061 2.720
SC
1.477 1.444 1.416 1.387 1.358 1.324
MODEL : MWM 015FR / MLC 015CR
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C kW 19.4 25 30 35 40 46
26.7 13.9 TC
3.283 3.117 2.970 2.822 2.674 2.497
SC
3.026 2.914 2.815 2.716 2.616 2.497
15 TC
3.537 3.330 3.146 2.961 2.776 2.555
SC
2.926 2.816 2.718 2.620 2.522 2.404
18 TC
4.232 3.912 3.626 3.340 3.054 2.711
SC
2.656 2.549 2.454 2.360 2.265 2.151
19.4 TC
4.556 4.183 3.850 3.517 3.184 2.784
SC
2.529 2.425 2.331 2.238 2.145 2.033
20 TC
4.695 4.311 3.967 3.624 3.281 2.869
SC
2.475 2.368 2.272 2.176 2.080 1.965
22 TC
5.158 4.736 4.359 3.982 3.605 3.153
SC
2.295 2.178 2.073 1.969 1.864 1.739
24 TC
5.621 5.161 4.751 4.340 3.929 3.436
SC
2.114 1.988 1.875 1.762 1.649 1.513
All the data above are based on 26.7°C entering DB. To obtain data for different entering DB, please use the formula below :
Sensible capacity (@EDB) = Sensible capacity (@26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
Where, BPF = Bypass factor
EDB = Entering dry bulb temperature, ° C
MWM 007FR MWM 010FR MWM 015FR
MLC 007CR MLC 010CR MLC 015CR
Bypass Factor
0.29 0.29 0.35