Specifications

26
R407C MODELS
(COOLING ONLY)
MODEL : MWM 007F / M4LC 007B
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C KW 19.4 25 30 35 40 46
26.7 13.9 TC
2.428 2.241 2.074 1.907 1.741 1.541
SC
2.428 2.241 2.074 1.907 1.741 1.541
15 TC
2.494 2.303 2.131 1.960 1.789 1.583
SC
2.321 2.156 2.010 1.863 1.717 1.541
18 TC
2.676 2.471 2.287 2.103 1.919 1.699
SC
2.029 1.926 1.835 1.743 1.652 1.542
19.4 TC
2.761 2.549 2.359 2.170 1.980 1.753
SC
1.892 1.819 1.753 1.687 1.621 1.542
20 TC
2.798 2.588 2.400 2.213 2.026 1.801
SC
1.834 1.761 1.697 1.632 1.568 1.490
22 TC
2.919 2.717 2.537 2.357 2.177 1.960
SC
1.639 1.571 1.510 1.449 1.388 1.315
24 TC
3.040 2.847 2.674 2.501 2.328 2.120
SC
1.445 1.381 1.323 1.266 1.209 1.140
MODEL : MWM 010F / M4LC 010B
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C KW 19.4 25 30 35 40 46
26.7 13.9 TC
2.559 2.415 2.286 2.157 2.028 1.873
SC
2.559 2.415 2.286 2.157 2.028 1.873
15 TC
2.694 2.536 2.395 2.253 2.112 1.942
SC
2.380 2.264 2.160 2.056 1.952 1.827
18 TC
3.063 2.867 2.691 2.516 2.340 2.129
SC
1.892 1.852 1.815 1.779 1.743 1.700
19.4 TC
3.235 3.021 2.830 2.638 2.447 2.217
SC
1.664 1.659 1.655 1.650 1.646 1.640
20 TC
3.309 3.090 2.893 2.696 2.500 2.264
SC
1.566 1.568 1.569 1.570 1.571 1.572
22 TC
3.555 3.317 3.104 2.890 2.677 2.421
SC
1.241 1.263 1.282 1.301 1.321 1.344
24 TC
3.801 3.544 3.314 3.084 2.854 2.578
SC
0.916 0.958 0.995 1.033 1.071 1.116
MODEL : MWM 015F / M4LC 015B
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C KW 19.4 25 30 35 40 46
26.7 13.9 TC
2.764 2.664 2.575 2.485 2.396 2.289
SC
2.661 2.583 2.513 2.443 2.373 2.289
15 TC
3.050 2.900 2.767 2.633 2.499 2.339
SC
2.593 2.509 2.435 2.360 2.286 2.196
18 TC
3.831 3.545 3.290 3.035 2.781 2.475
SC
2.406 2.309 2.222 2.136 2.049 1.945
19.4 TC
4.195 3.846 3.535 3.223 2.912 2.538
SC
2.319 2.216 2.123 2.031 1.938 1.827
20 TC
4.351 3.986 3.661 3.335 3.009 2.618
SC
2.282 2.174 2.077 1.981 1.884 1.768
22 TC
4.872 4.453 4.080 3.706 3.332 2.884
SC
2.157 2.034 1.923 1.813 1.703 1.570
24 TC
5.392 4.920 4.498 4.077 3.655 3.149
SC
2.033 1.894 1.770 1.646 1.522 1.373
All the data above are based on 26.7°C entering DB. To obtain data for different entering DB, please use the formula below :
Sensible capacity (@EDB) = Sensible capacity (@26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
Where, BPF = Bypass factor
EDB = Entering dry bulb temperature, ° C
MWM 007F MWM 010F MWM 015F
M4LC 007B M4LC 010B M4LC 015B
Bypass Factor
0.30 0.27 0.34