Specifications

27
MODEL : MWM 020F / M4LC 020B
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C kW 19.4 25 30 35 40 46 50 52 54
26.7 13.9 TC
4.970 4.725 4.507 4.288 3.881 3.600 3.464 3.411 3.369
SC
4.554 4.396 4.256 4.116 3.725 3.455 3.324 3.274 3.233
15 TC
5.199 4.949 4.726 4.503 4.076 3.780 3.637 3.582 3.537
SC
4.313 4.189 4.078 3.967 3.590 3.330 3.204 3.155 3.116
18 TC
5.824 5.560 5.325 5.089 4.606 4.272 4.110 4.048 3.998
SC
3.657 3.622 3.591 3.559 3.221 2.988 2.875 2.831 2.796
19.4 TC
6.115 5.845 5.604 5.363 4.854 4.502 4.331 4.265 4.212
SC
3.351 3.357 3.363 3.369 3.049 2.828 2.721 2.680 2.647
20 TC
6.240 5.955 5.700 5.445 4.928 4.571 4.398 4.331 4.277
SC
3.219 3.223 3.227 3.230 2.924 2.712 2.609 2.569 2.538
22 TC
6.656 6.321 6.021 5.721 5.178 4.803 4.621 4.551 4.494
SC
2.782 2.777 2.772 2.768 2.505 2.323 2.235 2.201 2.174
24 TC
7.073 6.687 6.342 5.997 5.428 5.034 4.844 4.770 4.711
SC
2.344 2.330 2.318 2.305 2.086 1.935 1.862 1.833 1.811
HIGH AMBIENT
MODEL : MWM 025F / M4LC 025B
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C kW 19.4 25 30 35 40 46 50 52 54
26.7 13.9 TC
5.224 5.044 4.884 4.723 4.578 4.345 4.233 4.190 4.156
SC
4.981 4.852 4.737 4.623 4.480 4.252 4.143 4.101 4.068
15 TC
5.780 5.503 5.256 5.009 4.855 4.608 4.490 4.445 4.408
SC
4.806 4.669 4.547 4.425 4.288 4.070 3.966 3.926 3.894
18 TC
7.295 6.755 6.273 5.790 5.612 5.327 5.190 5.137 5.096
SC
4.328 4.169 4.027 3.885 3.765 3.574 3.482 3.447 3.419
19.4 TC
8.002 7.339 6.747 6.155 5.965 5.662 5.517 5.461 5.416
SC
4.105 3.936 3.784 3.633 3.521 3.342 3.256 3.223 3.197
20 TC
8.305 7.610 6.990 6.369 6.173 5.859 5.708 5.651 5.605
SC
4.010 3.837 3.683 3.529 3.420 3.246 3.163 3.131 3.105
22 TC
9.316 8.514 7.798 7.083 6.865 6.516 6.348 6.284 6.233
SC
3.692 3.509 3.345 3.182 3.084 2.927 2.852 2.823 2.800
24 TC
10.326 9.418 8.607 7.797 7.557 7.173 6.988 6.918 6.861
SC
3.373 3.180 3.008 2.835 2.748 2.608 2.541 2.516 2.495
HIGH AMBIENT
MODEL : MWM 031F / M4LC 031C
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C kW 19.4 25 30 35 40 46 50 52 54
26.7 13.9 TC
7.791 7.422 7.091 6.761 6.437 6.099 5.835 5.692 5.542
SC
7.360 7.081 6.832 6.583 6.267 5.938 5.681 5.542 5.395
15 TC
8.255 7.843 7.476 7.109 6.768 6.412 6.135 5.985 5.827
SC
7.056 6.804 6.579 6.354 5.998 5.682 5.437 5.304 5.163
18 TC
9.518 8.993 8.525 8.057 7.671 7.268 6.954 6.783 6.604
SC
6.229 6.050 5.890 5.731 5.263 4.986 4.771 4.654 4.531
19.4 TC
10.107 9.530 9.015 8.500 8.092 7.667 7.336 7.156 6.966
SC
5.842 5.698 5.569 5.440 4.920 4.661 4.460 4.351 4.236
20 TC
10.360 9.755 9.216 8.676 8.260 7.826 7.488 7.304 7.111
SC
5.677 5.527 5.393 5.259 4.705 4.458 4.266 4.161 4.051
22 TC
11.202 10.506 9.884 9.263 8.819 8.356 7.995 7.799 7.592
SC
5.125 4.956 4.804 4.653 3.990 3.781 3.617 3.529 3.435
24 TC
12.044 11.256 10.553 9.851 9.378 8.885 8.502 8.293 8.074
SC
4.573 4.385 4.216 4.048 3.275 3.103 2.969 2.896 2.819
HIGH AMBIENT
All the data above are based on 26.7°C entering DB. To obtain data for different entering DB, please use the formula below :
Sensible capacity (EDB) = Sensible capacity (26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
Where, BPF = Bypass factor
EDB = Entering dry bulb temperature, ° C
MWM 020F
M4LC 020B
MWM 025F
M4LC 025B
MWM 031F
M4LC 031C
Bypass factor 0.35 0.36 0.32