Specifications

28
R407C MODELS
(HEATPUMP – COOLING MODE)
MODEL : MWM 007FR / M4LC 007BR
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C KW 19.4 25 30 35 40 46
26.7 13.9 TC
2.501 2.307 2.134 1.962 1.789 1.581
SC
2.501 2.307 2.134 1.962 1.789 1.581
15 TC
2.530 2.345 2.180 2.015 1.850 1.652
SC
2.359 2.198 2.054 1.910 1.766 1.594
18 TC
2.609 2.448 2.304 2.160 2.016 1.843
SC
1.973 1.900 1.835 1.770 1.705 1.627
19.4 TC
2.646 2.496 2.362 2.227 2.093 1.932
SC
1.793 1.761 1.733 1.705 1.676 1.642
20 TC
2.662 2.515 2.384 2.253 2.121 1.964
SC
1.716 1.687 1.661 1.635 1.609 1.579
22 TC
2.714 2.579 2.458 2.337 2.216 2.070
SC
1.458 1.439 1.421 1.404 1.386 1.365
24 TC
2.767 2.643 2.532 2.421 2.310 2.176
SC
1.201 1.191 1.182 1.172 1.163 1.152
MODEL : MWM 010FR / M4LC 010BR
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C KW 19.4 25 30 35 40 46
26.7 13.9 TC
2.521 2.384 2.262 2.140 2.018 1.872
SC
2.521 2.384 2.262 2.140 2.018 1.872
15 TC
2.698 2.533 2.387 2.240 2.093 1.917
SC
2.422 2.294 2.180 2.067 1.953 1.816
18 TC
3.179 2.939 2.725 2.510 2.296 2.039
SC
2.150 2.048 1.956 1.865 1.773 1.664
19.4 TC
3.404 3.129 2.883 2.637 2.391 2.096
SC
2.023 1.933 1.852 1.771 1.690 1.593
20 TC
3.501 3.218 2.966 2.713 2.461 2.158
SC
1.969 1.879 1.798 1.718 1.638 1.541
22 TC
3.822 3.516 3.242 2.969 2.695 2.367
SC
1.788 1.700 1.621 1.542 1.464 1.369
24 TC
4.143 3.813 3.519 3.224 2.930 2.576
SC
1.607 1.521 1.444 1.367 1.290 1.197
MODEL : MWM 015FR / M4LC 015BR
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C KW 19.4 25 30 35 40 46
26.7 13.9 TC
2.866 2.745 2.636 2.527 2.419 2.288
SC
2.774 2.672 2.580 2.489 2.398 2.288
15 TC
3.045 2.909 2.788 2.666 2.545 2.399
SC
2.641 2.559 2.486 2.412 2.339 2.251
18 TC
3.534 3.359 3.202 3.046 2.889 2.702
SC
2.278 2.251 2.227 2.203 2.179 2.151
19.4 TC
3.762 3.568 3.395 3.223 3.050 2.843
SC
2.109 2.108 2.107 2.106 2.105 2.104
20 TC
3.859 3.654 3.470 3.287 3.103 2.883
SC
2.036 2.032 2.028 2.024 2.020 2.015
22 TC
4.185 3.939 3.719 3.499 3.279 3.016
SC
1.794 1.779 1.764 1.750 1.736 1.719
24 TC
4.510 4.224 3.968 3.712 3.456 3.149
SC
1.552 1.525 1.501 1.477 1.453 1.424
All the data above are based on 26.7°C entering DB. To obtain data for different entering DB, please use the formula below :
Sensible capacity (@EDB) = Sensible capacity (@26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
Where, BPF = Bypass factor
EDB = Entering dry bulb temperature, ° C
MWM 007FR MWM 010FR MWM 015FR
M4LC 007BR M4LC 010BR M4LC 015BR
Bypass Factor
0.30 0.36 0.35