Instruction manual

94
PARAMETERS
4.2.21 Monitoring reference (Pr. 55, Pr. 56)
Pr. 55 "frequency monitoring reference"
Pr. 56 "current monitoring reference"
Set the frequency or current which is referenced when the output frequency or output
current is selected for terminal AM.
<Setting>
Refer to the above diagrams and set the frequency monitoring reference value in
Pr. 55 and the current monitoring reference value in Pr. 56.
Refer to the above diagrams and set the frequency monitoring reference value in
Pr. 55 and the current monitoring reference value in Pr. 56.
Pr. 55 is set when Pr. 158 = 0 and Pr. 56 is set when Pr. 158 = 1.
In Pr. 55 and Pr. 56, set the frequency and current at which the output voltage of
terminal AM will be 10V.
Parameter
Number
Factory
Setting
Setting
Range
55 60Hz 0 to 400Hz
56
Rated output
current
0 to 500A
Note: The maximum output voltage of terminal AM is 10VDC.
Pr. 158 "AM terminal function
selection"
Pr. 901 "AM terminal calibration"
Related parameters
Pr.55
Output or display
Output frequency
Pr.56
Output current
Output or display
10VDC (terminal AM)
10VDC (terminal AM)