Instruction manual

96
PARAMETERS
Note:1. Automatic restart after instantaneous power failure uses a reduced-voltage
starting system in which the output voltage is raised gradually with the
preset frequency unchanged, independently of the coasting speed of the
motor.
2. The SU and FU signals are not output during restart but are output after the
restart cushion time has elapsed.
CAUTION
When automatic restart after instantaneous power failure has been
selected, the motor and machine will start suddenly (after the reset time
has elapsed) after occurrence of an instantaneous power failure.
Stay away from the motor and machine.
When you have selected automatic restart after instantaneous power
failure, apply the supplied CAUTION seals in easily visible places.
When the start signal is turned off or the key is pressed during the
cushion time for automatic restart after instantaneous power failure,
deceleration starts after the automatic restart cushion time set in Pr. 58
"cushion time for automatic restart after instantaneous power failure" has
elapsed.
STOP
RESET
M4500E.book 96 ページ 2005年2月22日 火曜日 午後5時7分