Instruction manual

102
PARAMETERS
4.2.25 Retry function (Pr. 65, Pr. 67 to Pr. 69)
Pr. 65 "retry selection"
Pr. 67 "number of retries at alarm occurrence"
Pr. 68 "retry waiting time"
Pr. 69 "retry count display erasure"
When any protective function (major fault) is activated and the inverter stops its output,
the inverter itself resets automatically and performs retries. You can select whether retry
is made or not, alarms reset for retry, number of retries made, and waiting time.
<Setting>
Use Pr. 65 to select the protective functions (major faults) which execute retry.
Parameter
Number
Factory
Setting
Setting Range
65 0 0 to 3
67 0 0 to 10, 101 to 110
68 1 s 0.1 to 360 s
69 0 0
Errors Reset for
Retry
Setting
Display 0123
E.OC1

E.OC2 
E.OC3 
E.OV1 
E.OV2 
E.OV3 
E.THM
E.THT
E.FIN
E. BE
E. GF
E. LF
E.OHT
E.OLT
E.OPT
E. PE
E.PUE
E.RET
E.CPU
E.P24
E. 3
E. 6
E. 7
Note: indicates the retry items selected.
M4500E.book 102 ページ 2005年2月22日 火曜日 午後5時7分