PARAMETERS
Parameter details
(2) Tuning execution
For PU operation or combined operation 2, press the or key.
For external operation or combined operation 1, switch on the run command.
Parameter
Number
Setting Description
9 0 to 500A Set the rated motor current (A).
71 (Note)
0, 100 Thermal characteristics suitable for standard motor
1, 101 Thermal characteristics suitable for constant-torque motor
3, 103 Standard motor Select "offline
auto tuning
setting"
13, 113 Constant-torque motor
23, 123 Do not set.
5, 105 Standard motor
Star
connection
Direct input of
motor constants
enabled
15, 115 Constant-torque motor
6, 106 Standard motor
Delta
connection
16, 116 Constant-torque motor
83 0 to 1000V Set the rated motor voltage (V).
84 50 to 120Hz Set the rated motor frequency (Hz).
90
0 to 50
,
9999
Tuning data
(Values measured by offline auto tuning are set automatically.)
96
0 Offline auto tuning is not performed.
1 Offline auto tuning is performed.
Note: The electronic thermal relay function characteristics are also selected
simultaneously. By setting any of "100 to 123", the electronic thermal relay
function changes to the thermal characteristic of the constant-torque motor
when the RT signal switches on.
Note:1. To force tuning to end
• Switch on the MRS or RES signal or press the key to end.
• Switch off the tuning start command to make a forced end.
2. During offline auto tuning, only the following I/O signals are valid:
Input signals
<Valid signals>
MRS, RES, STF, STR
Output signals
RUN, AM, A, B, C
3. Special caution should be exercised when a sequence has been designed to
open the mechanical brake with the RUN signal.
FWD REV
STOP
RESET