PARAMETERS
<Setting items and set data>
After completion of parameter settings, set the instruction codes and data then start
communication from the computer to allow various types of operation control and monitoring.
No.
Item
Instruction
Code
Description
Number of
Data Digits
(Instruction
code
FF=1)
1
Operation
mode
Read
H7B
H0001: External operation
H0002: Communication operation
4 digits
Write
HFB
H0001: External operation
H0002: Communication operation
2
Monitoring
Output
frequency
[speed]
H6F
H0000 to HFFFF:Output frequency (hexadecimal)
in 0.01Hz increments
[Speed (hexadecimal) in r/min
increments if Pr. 37 = 1 to 9998]
4 digits
(6 digits)
Output
current
H70
H0000 to HFFFF:Output current (hexadecimal) in
0.01A increments
4 digits
Output
voltage
H71
H0000 to HFFFF:Output voltage (hexadecimal) in
0.1V increments
4 digits
Alarm
definition
H74 to
H77
H0000 to HFFFF:Two most recent alarm
definitions
Alarm definition display
example (instruction code H74)
Alarm data
4 digits
b15
b8b7
b0
001100 0 0 00000011
Previous alarm
(H30)
Most recent alarm
(HA0)
Data Description Data Description
H00 No alarm H80 GF
H10 OC1 H81 LF
H11 OC2 H90 OHT
H12 OC3 HA0 OPT
H20 OV1 HB0 PE
H21 OV2 HB1 PUE
H22 OV3 HB2 RET
H30 THT HC2 P24
H31 THM HF3 E. 3
H40 FIN HF6 E. 6
H60 OLT HF7 E. 7
H70 BE