Instruction manual

150
PARAMETERS
4.2.44 Cooling fan operation selection (Pr. 244)
Pr. 244 "cooling fan operation selection"
You can control the operation of the cooling fan built in the inverter (whether there is a
cooling fan or not depends on the models. Refer to the outline dimensional drawings
(page 193)).
<Setting>
<Reference>
In either of the following cases, fan operation is regarded as faulty, [FN] is shown on the
operation panel, and the minor fault (LF) signal is output. Use any of Pr. 190 to Pr. 192
(output terminal function selection) to allocate the terminal used to output the LF signal.
1) Pr. 244 = "0"
When the fan comes to a stop with power on.
2) Pr. 244 = "1"
When the inverter is running and the fan stops during fan ON command.
Parameter
Number
Factory
Setting
Setting
Range
244 0 0, 1
Setting Description
0
Operated at power on (independent of whether the inverter is running or
at a stop).
1
Cooling fan on-off control valid
(The cooling fan is always on while the inverter is running. During a stop,
the inverter status is monitored and the fan switches on-off according to
temperature.)
Note: When the terminal assignment is changed using Pr. 190 to Pr. 192, the other
functions may be affected. Confirm the functions of the corresponding
terminals before making settings.
M4500E.book 150 ページ 2005年2月22日 火曜日 午後5時7分