Instruction manual

182
MAINTENANCE/INSPECTION
Checking the inverter and converter modules
<Preparation>
(1) Disconnect the external power supply cables (R, S, T (L1, L2, L3)) and motor cables
(U, V, W).
(2) Prepare a meter. (Use 100
range.)
<Checking method>
Change the polarity of the meter alternately at the inverter terminals R (L1), S (L2),
T (L
3), U, V, W, P (+) and N (–), and check for continuity.
<Module device numbers and terminals to be checked>
(Assumes the use of an analog meter.)
Note:1. Before measurement, check that the smoothing capacitor is discharged
.
2. At the time of discontinuity, the measured value is almost . When there is
an instantaneous continuity, due to the smoothing capacitor the tester may
not indicate
. At the time of continuity, the measured value is several to
several ten's-of ohms depending on the number of modules, number of
parallel modules, circuit tester type, etc. If all measured values are almost
the same, the modules are without fault.
Tester Pol arity
Measured
Value
Tester Pol arity
Measured
Value
Converter
module
D1
R (L
1) P (+) Discontinuity
D4
R (L1) N (–) Continuity
P (+) R (L
1) Continuity N (–) R (L1) Discontinuity
D2
S (L
2) P (+) Discontinuity
D5
S (L2) N (–) Continuity
P (+) S (L
2) Continuity N (–) S (L2) Discontinuity
D3
T (L
3) P (+) Discontinuity
D6
T (L3) N (–) Continuity
P (+) T (L
3) Continuity N (–) T (L3) Discontinuity
Inverter module
TR1
U P (+) Discontinuity
TR4
U N (–) Continuity
P (+) U Continuity N (–) U Discontinuity
TR3
V P (+) Discontinuity
TR6
V N (–) Continuity
P (+) V Continuity N (–) V Discontinuity
TR5
W P (+) Discontinuity
TR2
W N (–) Continuity
P (+) W Continuity N (–) W Discontinuity
Converter module
Inverter module
D1 D2 D3
D4
D5 D6
TR1 TR3 TR5
TR4 TR6 TR2
U
V
W
C
R (L1)
S (L
2
)
T (L
3)
P (+)
N (-)