Instruction manual

33
2
INSTALLATION AND WIRING
2.2.6 Design information
1) When performing commercial power supply-inverter switch-over operation, securely
provide electrical and mechanical interlocks for the MC1 and MC2 used for
commercial power supply-inverter switch-over.
When there is a commercial power supply-inverter switch-over circuit as shown
below, the inverter will be damaged by leakage current from the power supply due to
arcs generated at the time of switch-over or chattering caused by a sequence error.
2) If the machine must not be restarted when power is restored after a power failure,
provide a magnetic contactor in the inverter's primary circuit and also make up a
sequence which will not switch on the start signal.
If the start signal (start switch) remains on after a power failure, the inverter will
automatically restart as soon as the power is restored.
3) Since the input signals to the control circuit are on a low level, use two or more
parallel micro signal contacts or a twin contact for contact inputs to prevent a contact
fault.
4) Do not apply a large voltage to the contact input terminals (e.g. STF) of the control
circuit.
5) Always apply a voltage to the alarm output terminals (A, B, C) via a relay coil, lamp
etc.
6) Make sure that the specifications and rating match the system requirements.
1) Commercial power supply-inverter
switch-over
3) Low-level signal contacts
Power
supply
Inverter
Leakage current
MC2
MC1
Interloc
k
U
V
W
IM
R (L
1
)
S (L
2
)
T (L
3
)
Low-level signal contacts Twin contac
t
M4500E.book 33 ページ 2005年2月22日 火曜日 午後5時7分