Instruction manual

65
4
PARAMETERS
Parameter List
General-purpose magnetic
flux vector control
80 Motor capacity (Note 6)
0.4 to 7.5kW,
9999
0.01kW 9999 115
82 Motor excitation current
0 to 500A,
9999
0.01A 9999 116
83
Rated motor voltage
(Note 6)
0 to 1000V 0.1V 575V 116
84
Rated motor frequency
(Note 6)
50 to 120Hz 0.01Hz (Note 3) 60Hz 116
90 Motor constant (R1)
0 to 50,
9999
0.001
9999 116
96
Auto-tuning setting/status
(Note 6)
0, 1 1 0 116
Communication functions
117
Communication station
number
0 to 31 1 0 122
118 Communication speed 48, 96, 192 1 192 122
119 Stop bit length
0, 1
(data length 8)
10, 11
(data length 7)
1 1 122
120
Parity check
presence/absence
0, 1, 2 1 2 122
121
Number of communication
retries
0 to 10, 9999 1 1 122
122
Communication check time
interval
0, 0.1 to
999.8 s, 9999
0.1s 9999 122
123 Waiting time setting
0 to 150,
9999
1 9999 122
124
CR LF presence/absence
selection
0, 1, 2 1 1 122
PID control
128 PID action selection
0, 20, 21,
50,51,60,61
1 0 135
129 PID proportional band
0.1 to 1000%,
9999
0.1% 100% 135
130 PID integral time
0.1 to 3600 s,
9999
0.1 s 1 s 135
131 Upper limit
0 to 100%,
9999
0.1% 9999 135
132 Lower limit
0 to 100%,
9999
0.1% 9999 135
133
PID action set point for PU
operation
0 to 100% 0.01% 0% 135
134 PID differential time
0.01 to
10.00 s, 9999
0.01 s 9999 135
Additional
function
145 Parameter for option (FR-PU04-MGI).
146 Parameter set by manufacturer. Do not set.
Current detection
150
Output current detection
level
0 to 200% 0.1% 150% 143
151
Output current detection
period
0 to 10 s 0.1 s 0 143
152 Zero current detection level 0 to 200.0% 0.1% 5.0% 144
153
Zero current detection
period
0.05 to 1 s 0.01 s 0.5 s 144
Func-
tion
Param-
eter
Number
Name
Setting
Range
Minimum
Setting
Increments
Factory
Setting
Refer
To:
Custo-
mer
Setting